1.
OVERVIEW OF THE ZPU-5000
The ZPU-5000 is a multi-channel acquisition and processing unit designed for monitoring large rotating units
such as turbo-generators, hydroelectric generators, and large motors. Each ZPU-5000 unit can simultaneously
monitor up to 16 high-speed parameters.
The modular construction of the ZPU-5000 unit supports up to eight two-channel analog input/output modules.
Each analog input/output module accomplishes several functions:
•
Applies a selected process on each input signal;
•
Detects alarms (performs comparisons between alert and danger threshold levels);
•
Determines the alarm type (increasing or decreasing value);
•
Controls four alarm relay driver outputs;
•
Outputs a processed raw value on two analog outputs (4 to 20 mA, and 0 to 10V);
•
Outputs a trend value on two analog outputs (4 to 20 mA, and 0 to 10V).
ZPU-5000 units are usually installed in a network configuration that includes at least a server and a database
engine. The network can also include workstations from which users can trigger manual measurements, view
in real-time the data collected, or analyze measurements.
The ZPU-5000 can also operate in a standalone configuration for basic real-time monitoring. In standalone
mode, the ZPU-5000 unit uses relay driver outputs to transmit notifications of alarm.
1.1 Supported software and types of measurements
Important Information
•
The information presented throughout this manual applies to ZOOM version 7.4 only.
When installed in a network configuration, ZPU-5000 units are linked to a server for connection to a database,
and to establish communication with other equipment. All operations are managed through ZOOM software
services:
ZOOM Server
to connect the ZPU-5000 unit to the database and to other ZOOM software
components.
ZOOM Application
to transmit the user’s commands for triggering measurements, display data
through real-time graphic displays, and provide software tools for analysis.
ZOOM Configuration
& ZOOM Update
to make configuration changes and transmit firmware updates that will be stored in
the ZPU-5000 internal memory.
ZPU-5000 Acquisition and Processing Unit with ZOOM Version 7.4 - User’s Manual
7
Содержание ZPU-5000
Страница 1: ...ZPU 5000 Acquisition and Processing Unit with ZOOM Version 7 4 User s Manual P N 9483 06M1A 240...
Страница 6: ...6 ZPU 5000 Acquisition and Processing Unit with ZOOM Version 7 4 User s Manual...
Страница 46: ...46 ZPU 5000 Acquisition and Processing Unit with ZOOM Version 7 4 User s Manual...