Boiler can be installed by a company holding a valid license to install and maintain the gas
appliances. A project according to the valid regulations must be prepared for installation.
The heating system must be filled with water, that meets the
Č
SN 07 7401 requirements, especially its
harness must not exceed the required parameters.
Recommended values
Hardness
mmol/l
1
Ca
2+
mmol/l
0,3
Concentration of total Fe + Mn
mg/l
(0,3)*
*) recommended value
WARNING!!! The use of anti-freeze mixture is not recommended by the manufacturer.
a) to the heating system
Č
SN 06 0310
Heating systems in buildings – Designing and installation
Č
SN 06 0830
Heating systems in buildings – protecting device
Č
SN 07 7401
Water and steam for thermal energy equipments with working pressure up to
8 MPa
EN 297
Gas – fired central heating boilers – Type B
11
and B
11BS
fitted with atmospheric
burners of nominal heat input not exceeding 70 kW
b) to the gas distribution
EN 1775
Gas supply - Gas pipework for buildings - Maximum operating pressure less
than or equal to 5 bar - Functional recommendations.
EN 12007-1
Gas supply systems – Pipelines for maximum operating pressure up to and
including 16 bar – Part 1: General functional recommendations
EN 12007-2
Gas supply systems – Pipelines for maximum operating pressure up to and
including 16 bar – Part 2: Specific functional recommendations for polyethylene
(MOP up to and including 10 bar)
EN 12007-3
Gas supply systems – Pipelines for maximum operating pressure up to and
including 16 bar – Part 3: Specific functional recommendations for steel
EN 12007-4
Gas supply systems – Pipelines for maximum operating pressure up to and
including 16 bar – Part 4: Specific functional recommendations for renovation
Č
SN 38 6405
Gas equipments. Operating principles
Č
SN 38 6462
Gas supply system - LPG - Pressure stations, distribution and consumption
Act no. 222/94 Coll.
on the conditions of enterprise and public service performance in power industry
sector and on the state energy inspection
c) to the chimney
Č
SN 73 4201
Chimneys and flue gas ducting– designing, implementation and connection of
fuel consumers.
d) regarding the fire regulations
Č
SN 06 1008
Fire safety of heat installations.
EN 13501-1 + A1
Fire classification of construction products and building elements – Part 1:
Classification using test data from reaction to fire tests.
e) to the system of HWS heating
Č
SN 06 0320
Heating systems in buildings – Hot water preparation – Designing and planning
Č
SN 06 0830
Heating systems in buildings – Safety devices.
Č
SN 75 5409
Water installations inside buildings
5.2
Positioning possibilities
Boiler can be installed in the basic environment AA5/AB5 according to
Č
SN 33 2000-1 ed. 2. It must
not be installed in zones 0,1 and 2 according to
Č
SN 33 2000-7-701 ed. 2.
The installation of the boiler must comply with all requirements of
Č
SN 06 1008.
Boiler positioning with regard to the fire regulations:
1. Positioning on the floor made of combustible material
−
Install the boiler on a incombustible thermally insulating pad exceeding the boiler ground-plan by
15 mm on all sides.
Содержание GRAND G 36
Страница 1: ...Hercules U26 N vod k obsluze VIADRUS GRAND G 36 MANUAL FOR BOILER OPERATION AND INSTALATION...
Страница 34: ...34...
Страница 36: ...36 Date of revision 16 2013 GB...
Страница 37: ...Hercules U26 N vod k obsluze VIADRUS GRAND G 36 MANUAL FOR BOILER OPERATION AND INSTALATION...
Страница 54: ...18...
Страница 58: ...22...
Страница 60: ...24 Date of revision 32 2013 GB...