GROUND FLOOR INSTALLATION
Recommended CHVK-58 Corner Horizontal
Vent Kit:
• Installation using cabinet surrounds
• Through wall using square termination
(up to 24" horizontal pipe)
• Corner installation (Using one 6" vertical
section, one 90° elbow and a maximum of
24" of horizontal pipe)
VENTING INSTALLATION
Continued
Figure 14 - Horizontal Termination
Configuration For Corner Installation
Using One 90° Elbow
Figure 15 - Horizontal Termination
Configuration with Vertical Rise and One
90° Elbow
Required
Vertical (V)
Vertical (V)
Vertical Pipe
Allowable
Horizontal (H)
51"
6"
26" Max.
57
1
/
4
" Min.
1'
30" Max.
69
1
/
4
" Min.
2'
74" Max.
81
1
/
2
" Min.
3'
98" Max.
94" Min.
4'
122" Max.
106" Min.
5'
146" Max.
159" Min.
9'
20' Max.
TO
H
Wall
Firestop
Straight/
Adjustable
Pipe 24" Max.
Horizontal
Square
Termination
90°
Elbow
Corner Installation
Vertical (V)
Horizontal (H)
51" Min.
32
1
/
2
" Max
90° Elbow
Wall
Firestop
Square
Termination
Not to Exceed
(H) Limits
As
Required
for (V),
See Chart
for Pipe
Section
Required
Horizontal Termination Configurations
Figures 14 through 18 show different con
-
figurations and alternatives for venting with
horizontal termination. Each figure includes a
chart with critical minimum and maximum di
-
mensions which MUST be met.
IMPORTANT
:
Remember that a horizontal run of venting
must have a 1/4" rise for every 12" of run
toward the termination.
Figure 16 - Square Termination
Clearance at Ground Floor Installation
12"