16
090433.01
Battery Monitor
3.4 Calibration
• Go to
Current
, see
‘2 Operation’
.
• Short-circuit connections 3 and 4 on
the converter.
• Calibrate the instrument if a current
is indicated of more than + or - 0.2 A.
• Press both push buttons simultane-
ously for at least 3 seconds to cali-
brate the instrument, see
‘5 Calibra-
tion current measurement’
.
• Remove the short-circuit and re-con-
nect the converter to the shunt.
3.5 Charge condition
Make sure that the battery is fully
charged
• Go to
Charge
, see
‘2 Operation’
.
• Press both push buttons simultane-
ously for at least 3 seconds to set 100
% charge condition, see
‘6 Setting
100 % charge condition’.
3.6 Setting alarms
3 different alarms can be set using the
instrument:
-
battery charge condition too low:
standard setting 20.0%
-
battery voltage too low:
standard setting 10.0 V
-
battery voltage too high:
standard setting 30.0 V
• Follow the directions given in
‘1 Sum-
mary Operation and Setup’
to set the
alarms.