6. Factory Default Settings
Parameter
Default Value
Minimum
Access Level
Action Threshold
0.14% obs/m (0.044% obs/ft)
Adm
Airflow…High Urgent
130%
Adm
Airflow…High Minor
120%
Adm
Airflow…Low Minor
80%
Adm
Airflow…Low Urgent
70%
Adm
Alarm Delays…Pre-Alarm
10 seconds
Adm
Alarm Delays…Alert
10 seconds
Adm
Alarm Delays…Fire
10 seconds
Adm
Alarms Latched
Latched
Adm
Alert Threshold
0.08% obs/m (0.025% obs/ft)
Adm
AutoLearn
14 days
0 Hours
0 Minutes
Adm
Adm
Adm
Button Lockout…Buttons
Enabled
Adm
Communications
Open-ended loop
Preferred Port
Network Delay
Health Check
None
A
15 seconds
45 seconds
Adm
Dst
Dst
Dst
Delay Times
Simultaneous/Cumulative
Adm
Device ID
Name/Location
Adm
Event Log to View
Smoke Level
Alarms
Faults
User Action
Adm
Adm
Adm
Adm
Faults Latched
Latched
Adm
Filter Service Interval
1825 days (5 years)
Adm
Fire Threshold
0.2% obs/m (0.062% obs/ft)
Adm
Full Scale
2.000% obs/m (0.61% obs/ft)
Adm
Instantaneous - Fire
Disabled
Adm
Loop Number (VN Version only)
0
Adm