CT33 User Manual v. X1.0 18
10
Tracing cables and wires indoors
10.1 Live and neutral electric cables
To connect transmitter to live targets, always use proper
contact proof safety class cords and adapters and follow
safety instructions.
WARNING! If either transmitter output terminal is
connected to a live target as shown in the figure, a
voltage appears on wires connected to the other
output as well, unless they are properly grounded.
Task: The route of a live or neutral cable must be
traced from a short distance, e.g. inside walls or on
cable shelves.
-
CTT33:
Connect transmitter between the wall socket N
and PE contacts (not to L contact) with the S3TB cord. This
method applies to situations where cable is disconnected
or a fuse has blown.