Warning

Do  not  connect  any  unit  to  an  electrical  supply  voltage  outside  of  the  specifica on.

This  document  refers  to  0-10  V  control  input.
In  some  cases  a  4-20  mA  control  input  may  have  been  provided.

Important

Supply  to  the  heater  should  be  1ph  or  3ph  and  a  neutral  -  refer  to  name  plate  for
correct  supply.

The  heater  is  fi ed  with  a  manual  reset  high  temperature  cutout  which  has  NC  (normally
closed)  terminals  and  an  air  flow  pressure  switch.  This  is  connected  in  series  with  the
main  contactor  coil  circuit,  to  remove  power  from  the  heater  in   the  event  of  over-
temperature or airflow failure. 

Under no circumstances is this circuit to be by passed.

Ensure  sufficient  earth  connec on  to  terminal  is  provided.

The  speed  controller  must  not  switch  off  fan  independent  of  control  system  or  allow
airflow  to  fall  below  stated  volume  on  the  electric  he ater  ba ery.

Fan  run  on  mer  r equired.  Turn  off  0-10  V  heat  demand  signal  2  minut es  before  fan
enable  signal.

Separate  cables  should  be  ins talled  for  0-10  VDC,  Control  signal  and  24  V AC  switched
enable  signal  in  c ompliance  BS7671/2018.

Warning

Cau on

Important

The  electrical  supply 

must  be  fully  isolated

  before  a emp ng  to  affect  any  work  on  this  unit.

All  electrical  connec ons  to  any  unit  must  be  carried  put  in  accordance  with  the  current
edi on  of  the  I.E. T  Regula ons,  only  c ompetent  Electricians  should  be  allo wed  to  affect  any
electrical  work  to  our  units.

Warning

It  is  the  cus tomer’s  responsibility  to  supply  earth  fault  protec on  through  the  bui lding
installa on  device  and  a  dedicated,  isolated  power  supply  with  overload  protec on.

Important

Important

Recommended
cable  entry  point

Recommended cable

entry point

Remove  Cover  before
making  cable  entry.

8

heatline

 Duct mounted Heaters

ecovent 

 

Duct Mounted Heaters

mini

Standard Wiring

& Installa on

5

It is recommended that the cable entry point should be at the end of the control sec on as shown in the figure 
below.
It is the responsibility of the installer to ensure that a suitable cable gland (giving adequate protec on and strain 
relief) is fi ed, and in doing so also ensure that no internal components are damaged during this installa on. 
Make certain all swarf is removed before use.

Fig. 

7

Содержание ecovent mini

Страница 1: ...rial Estate Chandlers Ford Eastleigh Hampshire SO53 4NF Tel 44 0 2380 46 11 50 email info ves co uk web www ves co uk Operation Maintenance Manual Duct Mounted Heaters mini VES Ref ID VES DSG 0010 Dec...

Страница 2: ...ature 3 Receipt of Goods Handling 4 Installa on 4 Standard Wiring Installa on 8 Maintenance 11 1 2 3 4 5 6 Contents Introduc on 1 The duct mounted heater ba eries bring wide versa lity to exis ng and...

Страница 3: ...n 1 Product EVCM ecovent mini 2 Hea ng Op on EH Electric hea ng HW Hot water coil 3 Size 1 size 1 ecovent mini 2 size 2 ecovent mini 4 Heater Size 0 5 to 3 0kW kW ra ng for EH 01 Coil op on 1 for HW 0...

Страница 4: ...hat access panels are not obstructed in any way and safe working access for maintenance must be provided in accordance with Health and Safety and Building Regula ons For con rma on of required access...

Страница 5: ...NF Tel 08448 15 60 60 ELECTRIC HEATER VES ANDOVER LTD Eagle Close Chandlers Ford Ind Est Eastleigh Hampshire SO53 4NF Tel 08448 15 60 60 ELECTRIC HEATER WARNING DISCONNECT THE MAINS SUPPLY BEFORE REMO...

Страница 6: ...20mm blind grommet which can be u lized Ensure adequate protec on and strain relief is given and in doing so also ensure that no internal components are damaged during this installa on Please note th...

Страница 7: ...tant that water and steam coils are protected against damage from extreme weather condi ons during the winter season If the water is allowed to freeze in the coil system damage may occur poten ally bu...

Страница 8: ...Control signal and 24 VAC switched enable signal in compliance BS7671 2018 Warning Cau on Important The electrical supply must be fully isolated before a emp ng to a ect any work on this unit All ele...

Страница 9: ...r contact VES Customer Services Department on 02380 46 11 50 quo ng the sales order SO number and unit type as found on the unit name plate Note Please refer to order acknowledgement for speci c contr...

Страница 10: ...m for full details or contact VES Customer Services Department on 02380 461150 quo ng the sales order SO number and quo ng the sales order SO number and unit type as found on the unit name plate Impor...

Страница 11: ...tly by a competent engineer Important Before a emp ng to carry out any maintenance work inves ga ve or repair work on our units the unit MUST BE COMPLETELY ISOLATED from its electrical supply Ensure a...

Страница 12: ...leigh Hampshire SO53 4NF Tel 44 0 2380 46 11 50 email info ves co uk web www ves co uk VES is a trading name of VES Andover Ltd Registered in England No 02303719 Registered Office as above VES Andover...

Отзывы: