Duct Mounted Heaters

mini

Con nued

On 

ecovent /-E

 units, an electric heater ba ery (EHB) will be installed. Supply to the heater

should be 1Phase or 3Phase with separate neutrals; confirma on of this can be found on the unit
nameplate. Cables should be of silicone rubber, fibreglass or of a similar high temperature
insulated type and be installed to current 

I.E.T. Regula ons

, ensuring a sufficient earth connec on

to the terminal provided. Care should be taken not to overstrain the terminal pillars as this may
permanently damage the elements.

The heater is fitted with a thermal cutout which will break contacts when the duct temperature

 rises above 70 °C.

It is important that the cutout is connected to the safety circuit so the heater is isolated in the
event of overhea ng caused by airflow failure.

The electrical supply must be isolated before a emp ng to reset the manual cut-out and should
be given sufficient  me to cool. For further informa on regarding electric heaters please see

VES Ref. ID431

.

If a speed controller is fitted to the system, it must not stop the fan independently of the control
system, or allow airflow to fall below the stated volume on the electric heater ba ery. Suitable
speed controllers without on/off switches are available from VES Andover.

Coils should be piped according to any relevant local codes of prac ce. Where threaded
connec ons are supplied, the only approved method of join ng method is by use of Boss white
and hemp. The thread fitted to the coil is to be supported at all  mes whilst making joints. All
external piping is to be supported independently from the coil. Fluid filters are recommended.

It is important that water and steam coils are protected against damage from extreme weather
condi ons during the win ter season. If the water is allowed to freeze in the coil system,
damage may occur poten ally burs ng pipes and resul ng in emergency problems.
Fit ng a frost thermostat at the unit inlet and ensuring that boilers run con nuously in low
ambient temperatures can help to prevent damage.

Hea ng coils do not cool immediately when the hot water supply is cut off. The residual heat
must be dissipated to avoid damage. The con nuous running of the fan a er shutdown
resolves this, by opera on of a run-on  mer.
The recommended length of run-on is 

2 minutes minimum

.

On 

ecovent

 

/ -W

 units, a Low Pressure Hot Water (LPHW) coil will be installed. The coils are

normally suitable for LPHW at 80 °C flow and 60 °C return temperature (see the unit outline
drawing for confirma on). LPHW coils are supplied as standard with an air vent and drain plug
located on the pipe work immediately adjacent to the coil connec ons on the AHU. The air vent
should be at the highest point, with the drain at the lowest. The coil should be regularly vented so
as to avoid poten al air locks, resul ng  in a fall in duty.

Typical LPHW Coil

Fig. 

6

Cau on

Coils

Electric Heater

Ba eries

Cau on

LPHW Coils

Flow

Return

Cau on

It is recommended that a check be made as to
whether any treatment is required to the water
supply for preven on of corrosion and scaling of
the equipment. Informa on regarding the necessary
ac on to be taken can be obtained from the relevant
Local Water Supply Authority.

The unit will have been supplied with connec ons
either le  or right-hand side looking in direc on of
airflow. Please see order acknowledgement for
confirma on of this handing. Should you need to
alter this please consult VES as unit adjustment may
invalidate  your  warranty.

Airflow

Installa on 4

Содержание ecovent mini

Страница 1: ...rial Estate Chandlers Ford Eastleigh Hampshire SO53 4NF Tel 44 0 2380 46 11 50 email info ves co uk web www ves co uk Operation Maintenance Manual Duct Mounted Heaters mini VES Ref ID VES DSG 0010 Dec...

Страница 2: ...ature 3 Receipt of Goods Handling 4 Installa on 4 Standard Wiring Installa on 8 Maintenance 11 1 2 3 4 5 6 Contents Introduc on 1 The duct mounted heater ba eries bring wide versa lity to exis ng and...

Страница 3: ...n 1 Product EVCM ecovent mini 2 Hea ng Op on EH Electric hea ng HW Hot water coil 3 Size 1 size 1 ecovent mini 2 size 2 ecovent mini 4 Heater Size 0 5 to 3 0kW kW ra ng for EH 01 Coil op on 1 for HW 0...

Страница 4: ...hat access panels are not obstructed in any way and safe working access for maintenance must be provided in accordance with Health and Safety and Building Regula ons For con rma on of required access...

Страница 5: ...NF Tel 08448 15 60 60 ELECTRIC HEATER VES ANDOVER LTD Eagle Close Chandlers Ford Ind Est Eastleigh Hampshire SO53 4NF Tel 08448 15 60 60 ELECTRIC HEATER WARNING DISCONNECT THE MAINS SUPPLY BEFORE REMO...

Страница 6: ...20mm blind grommet which can be u lized Ensure adequate protec on and strain relief is given and in doing so also ensure that no internal components are damaged during this installa on Please note th...

Страница 7: ...tant that water and steam coils are protected against damage from extreme weather condi ons during the winter season If the water is allowed to freeze in the coil system damage may occur poten ally bu...

Страница 8: ...Control signal and 24 VAC switched enable signal in compliance BS7671 2018 Warning Cau on Important The electrical supply must be fully isolated before a emp ng to a ect any work on this unit All ele...

Страница 9: ...r contact VES Customer Services Department on 02380 46 11 50 quo ng the sales order SO number and unit type as found on the unit name plate Note Please refer to order acknowledgement for speci c contr...

Страница 10: ...m for full details or contact VES Customer Services Department on 02380 461150 quo ng the sales order SO number and quo ng the sales order SO number and unit type as found on the unit name plate Impor...

Страница 11: ...tly by a competent engineer Important Before a emp ng to carry out any maintenance work inves ga ve or repair work on our units the unit MUST BE COMPLETELY ISOLATED from its electrical supply Ensure a...

Страница 12: ...leigh Hampshire SO53 4NF Tel 44 0 2380 46 11 50 email info ves co uk web www ves co uk VES is a trading name of VES Andover Ltd Registered in England No 02303719 Registered Office as above VES Andover...

Отзывы: