Check Procedure (Older Style Bays Only)
1.
With the PCU removed, use a quality wooden carpenter’s ruler or other non-conductive rule. Place the
measuring device directly against the unpainted bracket holding the AC/Data connector. Take two
measurements, one on the bottom of connector directly next to the bolt through the black ac housing,
and note the distance to the front outside of the left side panel. Take second measurement on the top
of the AC/Data connector. Both must measure 15-5/16” + 1/16” or -1/16” tolerance. See
Figure 7:
Taking Measurements
2.
Pay close attention to the measurements, they must be within 15-1/4” to 15-3/8”. If a measurement is
greater than 15-3/8” or less than 15-1/4”, adjustment is required (see next procedure).
Adjustment Procedure (Older Style Bays Only, if required)
1.
When adjustment of the PCU slot is required, it is recommended to remove the PCU below the slot
which requires adjustment. This allows the AC/Data connector to be moved as required to properly set
the 15-5/16” measurements.
NOTE!
The MCA will alarm with the removal of any PCU, so be aware Minor and Major alarms could be
generated during this process.
2.
In the PCU slot to be adjusted, remove the rear sheet metal panel on the rear of bay and locate the two
Philips 1/4” self tapping screws at the bottom of panel, which holds the AC connector. Loosen these
screws. See
3.
Directly to the right of the two Philips screws is a single 1/4” inch hex bolt which also must be loosened
for lower adjustment. See