![Vertiv NetSure V200D50 Скачать руководство пользователя страница 11](http://html1.mh-extra.com/html/vertiv/netsure-v200d50/netsure-v200d50_installation-and-user-manual_1008119011.webp)
Vertiv
|
NetSure V200D50 DC Power Retrofit Installation & User Manual (UM486527803)
|
Rev. F
11
Typical Input Data: One (1) V200D50 Retrofit, 60 Hz input.
a)
System output is initially adjusted to 54.48 volts DC as measured at the system sense point at 50% of
full load and nominal input. “Percent of Full Load” refers to percent of 180 Amperes.
Nominal
Input
Voltage
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
Efficiency
%
Heat
Dissipation
(BTU/Hr)
208
0
0.908
328.9
61.7
0.187
--
211
25
7.41
2672
2594.5
97.10
94.50
486
50
14.34
5171
5130
99.20
95.70
752
75
21.34
7694
7669
99.70
95.60
1161
100
28.87
10412
10395
99.80
94.60
1910
110
31.298
11285
11270
99.86
94.40
2139
120
31.23
11263
11246
99.84
93.88
2348
240
0
1.005
417
61.0
0.146
--
208
25
6.51
2709
2609.5
96.30
94.80
462
50
12.53
5218
5143
98.60
96.00
696
75
18.54
7717
7671
99.39
95.90
1069
100
24.893
10363
10329
99.67
95.26
1670
110
26.96
11223
11192
99.72
94.87
1940
120
26.918
11205
11170
99.69
94.40
2131
b)
Maximum Input Current: at 100% of full load with output adjusted to 58 volts DC as measured at the
Retrofit output terminals, and input voltage as shown.
Nominal
Input Voltage
Input
Voltage
Input Current
(Amperes)
208/240
176
36.33