Typical Input Data: One (1) V200D50 Retrofit, 50 Hz input.
a)
System output is initially adjusted to 54.48 volts DC as measured at the system sense point at 50% of
full load and nominal input. “Percent of Full Load” refers to percent of 180 Amperes.
Nominal
Input
Voltage
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
Efficiency
%
Heat
Dissipation
(BTU/Hr)
208
0
0.815
294
61
0.20
--
211
25
7.410
2669
2607
97.66
94.68
473
50
14.320
5160
5126
99.36
95.67
757
75
21.500
7751
7731
99.74
95.57
1169
100
28.850
10403
10388
99.86
94.73
1869
110
31.280
11284
11269
99.88
94.30
2192
120
31.280
11280
11266
99.87
93.80
2383
240
0
0.895
373
61
0.16
--
208
25
6.504
2709
2630
97.10
95.07
450
50
12.470
5195
5138.6
98.92
96.07
689
75
18.500
7706
7670
99.50
95.90
1071
100
24.890
10364
10338
99.74
95.20
1679
110
26.950
11220
11195
99.78
94.88
1954
120
26.940
11217
11190
99.76
94.40
2138
a)
Maximum Input Current: at 100% of full load with output adjusted to 58 volts DC as measured at the
Retrofit output terminals, and input voltage as shown.
Nominal
Input Voltage
Input
Voltage
Input Current
(Amperes)
208/240
176
36.47