Vertiv
|
NetSure V200D50 DC Power Retrofit Installation & User Manual (UM486527803)
|
Rev. F
21
Figure 8:
Locating the Bottom Two 1/4” Self Tapping Screws and 1/4” Hex Bolt
4.
Next loosen the two Philips 1/4” self tapping screws at the top of the PCU position to be adjusted. See
Figure 9:
Locating the Top Two 1/4” Self Tapping Screws
5.
With hardware loosened, measure the bottom first for a 15-5/16” and secure the single 1/4” hex bolt first.
6.
With bottom secured at 15-5/16”, move to the top of the AC connector and measure for 15-5/16”, then
secure the two Philips screws at the top of the back plane sheetmetal.
NOTE!
The process of measurement and securing the hardware may take two people to keep the panel
from moving when retorqueing the hardware.
7.
Torque the top and bottom 1/4” screws (2 each) and bottom 1/4” bolt to 84 in-lbs.
8.
Recheck the measurements by performing the previous procedure to verify the proper measurements.
Loosen These
Loosen These