DESCRIPTION
A 1RU high by 19” wide distribution fuse panel with twenty (20) fuse load positions.
Provides…
•
+24 VDC or -48 VDC distribution fuse panel.
•
Dual (Side A and Side B) load distribution.
•
19” and 23” relay rack mounting options.
•
(20) fuse load distribution positions (0.180 A to 20 A), (10) per side.
•
Two (2) input connection points, per side.
•
Local alarm/status indicators (Feed A Power, Feed B Power, Feed A FA, Feed B FA, Major, and Minor).
•
Alarm relay contacts (Major, Minor, A Power Fail, B Power Fail, and FA) for connection to external alarms.
•
Resistive battery (+24 Batt FA and -48 Batt FA) for connection to external alarms.
SPECIFICATIONS
Electrical
1.
Input / Output Voltage: N24 VDC or -48 VDC
(Feed A and Feed B must be of the same voltage).
2.
Maximum Input Current: 100 A per side, 200 A total.
3.
Maximum Load Distribution Current:
a)
100 A per side, 200 A total at @ +55 °C (+131 °F).
b)
80 A per side, 160 A total @ +65 °C (+149 °F).