Vertiv
|
200 A Distribution Fuse Panel Assembly Installation & User Manual (UM563317)
|
Rev. B
8
4.
Maximum Fuse Size: 20 A.
5.
Local Alarm / Status Indicators:
a)
Major
b)
Minor
c)
Feed A Power
d)
Feed B Power
e)
Feed A FA
f)
Feed B FA
6.
External Form-C Alarm Relay Contacts:
a)
Major (110 VDC maximum, 33 W maximum, 33 W/60 VDC = 0.55 A maximum)
b)
Minor (110 VDC maximum, 33 W maximum, 33 W/60 VDC = 0.55 A maximum)
c)
A Power Fail (120 VDC maximum, 60 W maximum, 60 W/60 VDC = 1 A maximum)
d)
B Power Fail (120 VDC maximum, 60 W maximum, 60 W/60 VDC = 1 A maximum)
e)
FA (120 VDC maximum, 60 W maximum, 60 W/60 VDC = 1 A maximum)
7.
Resistive Battery for External Alarm Circuits:
a)
+24 Batt FA
b)
-48 Batt FA
Environmental
1.
Operating Ambient Temperature Range: -40 °C to +65 °C (-40 °F to +149 °F).
2.
Storage Ambient Temperature Range: -40 °C to +70 °C (-40 °F to +158 °F).
3.
Relative Humidity: Capable of operating in an ambient relative humidity range of 0% to 95%, non-
condensing.
4.
Altitude: Capable of operating in an altitude range of -200 feet to 10,000 feet. The maximum operating
ambient temperature should be de-rated by 3 °C per 1000 feet above 6562 feet.
Compliance Information
1.
Safety Compliance (pending): This panel is UL Recognized for use in DC Power Distribution Centers for
Communications Equipment.
2.
NEBS Compliance (pending): Compliance verified by a Nationally Recognized Testing Laboratory
(NRTL) per GR-1089-CORE and GR-63-CORE. Contact Vertiv for NEBS compliance reports.
3.
GR-3108 (Pending): GR-3108 Class 2 Compliant.
Содержание NetSure NSFP200