Vertiv™ NetSure™ ITS 12V DC Power Shelf Installation & User Manual 

 vi 

Important Safety Instructions 

Safety Admonishments Definitions 

Definitions of the safety admonishments used in this document are listed under “Admonishments Used in this Document” on page v. 

 

General Safety 

 

DANGER!  

YOU MUST FOLLOW APPROVED SAFETY PROCEDURES. 

Performing the following procedures may expose you to hazards.  These procedures should be performed by qualified 
technicians familiar with the hazards associated with this type of equipment.  These hazards may include shock, energy, 
and/or burns.  To avoid these hazards: 

a)

 

The tasks should be performed in the order indicated. 

b)

 

Remove watches, rings, and other metal objects. 

c)

 

Prior to contacting any uninsulated surface or termination, use a voltmeter to verify that no voltage or the expected 
voltage is present.  Check for voltage with both AC and DC voltmeters prior to making contact. 

d)

 

Wear eye protection. 

e)

 

Use certified and well-maintained insulated tools.  Use double insulated tools appropriately rated for the work to be 
performed. 

 

Voltages 

AC Input Voltages 

 

DANGER!  

This system operates from AC input voltage capable of producing fatal electrical shock.  AC input power must be 

completely disconnected from the branch circuits wiring used to provide power to the system before any AC electrical 
connections are made.  Follow local lockout/tagout procedures to ensure upstream branch circuit breakers remain de-
energized during installation.  DO NOT apply AC input power to the system until all electrical connections have been 
completed and checked. 

 

DC Output and Battery Voltages 

 

DANGER!  

This system produces DC power and may have a battery source connected to it.  Although the DC voltage is not 

hazardously high, the rectifiers and/or battery can deliver large amounts of current.  Exercise extreme caution not to 
inadvertently contact or have any tool inadvertently contact an output terminal or battery terminal or exposed wire 
connected to an output terminal or battery terminal.  NEVER allow a metal object, such as a tool, to contact more than one 
termination or battery terminal at a time, or to simultaneously contact a termination or battery terminal and a grounded 
object.  Even a momentary short circuit can cause sparking, explosion, and injury. 

 

DANGER!  

Follow local lockout/tagout procedures to ensure DC branch circuit protection devices remain de-energized 

during installation at loads, as required. 

Содержание NetSure ITS Series

Страница 1: ...NetSure ITS Series 12V DC Power Shelf Installation and User Manual Specification Number 588706100 Model Number PSS12 2200 19BC PSS12 2200 19B...

Страница 2: ...ming procedures not specifically described in this document The products covered by this instruction manual are manufactured and or sold by Vertiv This document is the property of Vertiv and contains...

Страница 3: ...tions 9 5 5 1 External Alarm Reference Monitoring and Control Connection Points Locations 9 5 5 2 Remote Sense not implemented at this time 9 5 5 3 EPO Signal 9 5 5 4 Imminent Power Fail Alarm 9 5 5 5...

Страница 4: ...Vertiv NetSure ITS Series 12V DC Power Shelf Installation User Manual iv 10 5 Replacement Procedures 26...

Страница 5: ...voided ANSI OSHA This admonition is not used for situations that pose a risk only to equipment data or service even if such use appears to be permitted in some of the applicable standards OSHA ALERT A...

Страница 6: ...s from AC input voltage capable of producing fatal electrical shock AC input power must be completely disconnected from the branch circuits wiring used to provide power to the system before any AC ele...

Страница 7: ...rdous Voltage DANGER HAZARD OF ELECTRICAL SHOCK More than one disconnect may be required to de energize the system before servicing Handling Equipment Containing Static Sensitive Components ALERT Inst...

Страница 8: ...sistor is necessary Read and follow wrist strap manufacturer s instructions outlining use of a specific wrist strap 3 Do not touch traces or components on equipment containing static sensitive compone...

Страница 9: ...across all module mounting assemblies and all rectifiers load share and all rectifiers are load managed via the SCC In installations with all main module mounting assemblies each module mounting asse...

Страница 10: ...procedures may have been performed at the factory for you Installing the System Equipment Inspection Completed Module Mounting Assembly s Mounted in an IT Rack Making Electrical Connections System Fra...

Страница 11: ...her with no space between them 4 2 Inspecting the Equipment and Storing for Delayed Installations 4 2 1 Inspecting the Equipment General Compare the contents of the shipment with the bill of lading Re...

Страница 12: ...n Compute IT rack version 2 rack 2 Slide the module mounting assembly into the front of the IT rack resting the bottom of the module mounting assembly on the mounting rails installed in the IT rack 3...

Страница 13: ...IPPING SUPPORT BRACKET BEFORE POWERING SYSTEM Procedure 1 Insert rectifier modules and SCC controller into the module mounting assembly For SCC controller installation instructions refer to SCC Contro...

Страница 14: ...l Standards Institute ANSI approved National Fire Protection Association s NFPA National Electrical Code NEC applicable local codes and your specific site requirements For operation in countries where...

Страница 15: ...e mounting assemblies all module mounting assemblies are on one DC bus and are controlled by a single SCC controller A common CAN bus is shared across all module mounting assemblies and all rectifiers...

Страница 16: ...180 in lbs Rear List 01 Shown other Lists Similar 12V DC Bus Top 3 places GND Return Bus Bottom 3 places Rear List 01 Shown other Lists Similar Busbar shield removed for clarity only 12V DC Bus Top 3...

Страница 17: ...e to shut down the rectifiers Refer to Figure 5 3 5 5 4 Imminent Power Fail Alarm Contacts close between J1 1 and J1 2 when an imminent power fail alarm occurs This alarm signals when the combination...

Страница 18: ...y is controlled by contains a separate SCC controller A separate CAN bus exists per module mounting assembly rectifiers load share per module mounting assembly and rectifiers are load managed via an S...

Страница 19: ...customer to install conduit or cord grips using the AC input access hole in the rear of the shelf and wire to the AC input terminal block located behind the rear access cover See Figure 5 5 See Syste...

Страница 20: ...r recommended wire size and branch circuit protection device rating Figure 5 6 AC Input Connections to a 588706100 List 02 Module Mounting Assembly Hardwired AC Input Connections 588706100 List 02 Har...

Страница 21: ...circuit protection device rating Figure 5 7 AC Input Connections to a 588706100 List 03 List 13 Module Mounting Assembly Hardwired AC Input Connections 588706100 List 03 List 13 Hardwired Nominal 230...

Страница 22: ...mended wire size and branch circuit protection device rating Figure 5 8 AC Input Connections to a 588706100 List 05 List 15 Module Mounting Assembly Hardwired AC Input Connections 588706100 List 05 Li...

Страница 23: ...ine Cord Integration For Use With 588706100 List 01 Nominal 208 VAC 240 VAC 50 Hz 60 Hz 3 Phase 1 Feed per Module Mounting Assembly 1 Feed per 9 Module Positions AC Feed Positions 1 9 208 VAC 240 VAC...

Страница 24: ...ire X Black Wire W No Connection Z Red Wire RPT404001 5 NEMA L21 30P Twist Lock Plug 30 A AC Feed 2 Positions 7 9 208 VAC 50 Hz 60 Hz Three Phase L1 L2 Position 7 L2 L3 Position 8 L1 L3 Position 9 L1...

Страница 25: ...01 Nominal 208 VAC 240 VAC 50 Hz 60 Hz 3 Phase 1 Feed per Module Mounting Assembly 1 Feed per 9 Module Positions AC Feed Positions 1 9 208 VAC 240 VAC 50 Hz 60 Hz Three Phase L1 L2 Position 1 4 7 L2...

Страница 26: ...ons 1 Feed per 3 Module Positions AC Feed 2 Positions 7 9 208 VAC 240 VAC 50 Hz 60 Hz Three Phase L1 L2 Position 7 L2 L3 Position 8 L1 L3 Position 9 L1 L3 Convenience Outlet 1 AC Feed 1 Positions 1 6...

Страница 27: ...or equivalent AC Line Cord P N 149068 length in feet as ordered 4 AWG AC Input Connections 588706100 List 460 AC Line Cord Integration For Use With 588706100 List 01 Nominal 208 VAC 240 VAC 50 Hz 60...

Страница 28: ...3 Phase 1 Feed per Module Mounting Assembly 1 Feed per 9 Module Positions AC Input Connections 588706100 List 532 AC Line Cord Integration 8 AWG AC Line Cord P N TFV204001 3 length in feet as ordered...

Страница 29: ...nt d on next page AC Line Cord P N 149642 for 277 480VAC input AC Line Cord P N 149588 for 230 400 or 240 415VAC input AC Input Connections 588706100 List 560 AC Line Cord Integration 6 AWG Green Wire...

Страница 30: ...3 Phase 1 Feed per Module Mounting Assembly 1 Feed per 9 Module Positions AC Feed Positions 1 9 277 VAC 480 VAC 4 Wire PE 50 Hz 60 Hz Three Phase L1 N Position 1 4 7 L2 N Position 2 5 8 L3 N Position...

Страница 31: ...tructions CAUTION Performing various steps in the following procedures may cause a service interruption and or result in the extension of alarms Notify any appropriate personnel before starting these...

Страница 32: ...ing the bottom of the cover out and up then slide down to release the top tabs 4 The system is pre configured Refer to the master upstream supervisory and control unit also known as the Rack Managemen...

Страница 33: ...fiers When a yellow or red LED is illuminated on a rectifier the SNMP data from the controller can be used to identify the specific problem 8 2 Local Indicators SCC Controller and Rectifier Module Ref...

Страница 34: ...isolate failure to a specific element Once the faulty element has been identified refer to Replacement Information on page 26 and Replacement Procedures on page 26 10 4 Replacement Information When a...

Страница 35: ...S Series 12V DC Power Shelf Installation User Manual Connect with Vertiv on Social Media https www facebook com vertivI https www instagram com vertiv https www linkedin com company vertiv https www t...

Страница 36: ...are trade names trademarks or registered trademarks of their respective owners While every precaution has been taken to ensure accuracy and completeness here Vertiv Group Corp assumes no responsibilit...