![Vertiv NetSure ITS Series Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/vertiv/netsure-its-series/netsure-its-series_installation-and-user-manual_1008117030.webp)
Vertiv™ NetSure™ ITS 12V DC Power Shelf Installation & User Manual
22
List 560 AC Input Cable Integration (cont’d from previous page)
AC Input Connections, 588706100 List 560, AC Line Cord Integration
For Use With 588706100 List 05, 15
Nominal 277 VAC / 480 VAC, 4-Wire + PE, 50 Hz / 60 Hz, 3-Phase,
1 Feed per Module Mounting Assembly
(1 Feed per 9 Module Positions)
AC Input Connections, 588706100 List 560, AC Line Cord Integration
For Use With 588706100 List 03, 13
Nominal 230 VAC / 400 VAC or 240 VAC / 415 VAC, 4-Wire + PE, 50 Hz / 60 Hz, 3-Phase,
1 Feed per Module Mounting Assembly
(1 Feed per 9 Module Positions)
AC Feed
(Positions #1 - #9)
277 VAC / 480 VAC,
4-Wire + PE, 50 Hz / 60 Hz, Three Phase
L1 - N: Position #1, #4, #7
L2 - N: Position #2, #5, #8
L3 - N: Position #3, #6, #9
L2 (Red Wire)
GND (Green Wire)
L1 (Orange Wire)
L3 (Black Wire)
N (White Wire)
RPT404001/6
IEC, 4P5W, 60 A
Hubbell HBL560P7W
(or equivalent)
AC Feed
(Positions #1 - #9)
230 VAC / 400 VAC or 240 VAC / 415 VAC,
4-Wire + PE, 50 Hz / 60 Hz, Three Phase
L1 - N: Position #1, #4, #7
L2 - N: Position #2, #5, #8
L3 - N: Position #3, #6, #9
L3 - N: Convenience Outlet #2
L1 - N: Convenience Outlet #1
L2 (Red Wire)
GND (Green Wire)
L1 (Orange Wire)
L3 (Black Wire)
N (White Wire)
RPT404001/7
IEC, 4P5W, 60 A
Hubbell HBL560P6W
(or equivalent)
AC Input Connections, 588706100 List 560, AC Line Cord Integration