Vertiv™ NetSure™ External Distribution Box (EDB) Description and Installation Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
4
•
Short Circuit Current: 10000 ADC.
•
Maximum Load Distribution Circuit Breaker Size: 60 A.
•
Circuit Breaker Alarm (CBA) Circuit: A set of Form-C alarm relay contacts and resistive battery are provided for connection
to external CBA alarms. Relay contacts rated for 2 A @ 30 VDC, 0.6 A @ 110 VDC, and 0.6A @ 125 VAC.
2.4.2
Environmental
•
Operating Ambient Temperature Range: -40
°
F to +115
°
F (–40
°
C to +46
°
C).
•
Storage Ambient Temperature Range: –40
°
F to +185
°
F (–40
°
C to +85
°
C).
•
Relative Humidity: Capable of operating in an ambient relative humidity range of 0 % to 95 %, non-condensing.
•
Altitude: Capable of operating in an altitude range of 0 feet to 10,000 feet.
2.4.3
Compliance information
The Vertiv™ NetSure™ External Distribution Box (EDB) complies with the following standards:
•
UL Listed to UL 62368-1 (2nd Edition), UL Subject 1801, and CAN/CSA C22.2 No. 62368-1-14 (2nd Edition) under Vertiv file
no. E97066 (QPQY/QPQY7 categories).
•
UL-50E Rain Test.
2.4.4
Safety listed AC and DC components
A typical Vertiv™ NetSure™ External Distribution Box (EDB) includes listed or recognized components for the United States.
2.4.5
Enclosure dimensions, weights, and physical specifications
Dimensions
•
See Figure 2.2 for overall dimensions.
•
See Figure 2.3 for mounting hole dimensions.
Physical Specifications and Weight
•
Height: 60.82 inches.
•
Width: 40.00 inches.
•
Depth: 9.12 inches.
•
Weight: 135 lbs.
•
Color: Cool White.
2.5
Local DC Power Source
DC power to be provided by customer via an upstream power source, typically from an adjacent enclosure.