5
1.7. Environmental Requirements
1.7.1. Operating Environment
The operating environment of the Vertiv
™
Liebert® XDO unit meets the requirements of GB4798.3-2007,
.
Table 1-2 Operating Environment Requirements
Items
Requirements
Ambient temperature
Indoor
18˚C to 40˚C, RH<60%
Unit protection level
IP20
Altitude
1000 m, more than 1000 m, please contact Vertiv local representative
Operating voltage range
220 V to 240 V ±10%, 50 Hz / 60 Hz, 1 N~
Pollution level
Level II
1.7.2. Storage Environment
The storage environment of the Liebert XDO unit meets the requirements of GB4798.1-2005,
Table 1-3 Storage Environment Requirements
Items
Requirements
Storage environment
Indoor, clean (no dust)
Environment humidity
< 95% RH
Ambient temperature
-25˚C to +55˚C
Storage time
The total transportation and storage time does not exceed 6 months, and the
performance needs to be re-calibrated after 6 months