225-600kVA Installation Manual | Rev. 8 | 07/2017
27
Figure 11
225-300kVA low-voltage cable routing
NOTE
Remove the low-voltage control wire plate (at the top of the unit and then expose the area by removing the
inside cover plate), punch the conduit holes, land the conduit, and then route the control wire to the “chimney
stack” toward the bottom of the unit.
Run the control wires to through the conduit plate provided. If the unit is not on a raised floor, then insert a
rubber grommet into the conduit plate hole (at the bottom of the entry location for the low-voltage control
wiring).
Low-Voltage
Top Entry
Low-Voltage
Bottom Entry
Doors and
Inner Skins
Removed
Top Entry,
Low-Voltage
Cable Raceway