![Vertiv Liebert NX 225 kVA Скачать руководство пользователя страница 22](http://html.mh-extra.com/html/vertiv/liebert-nx-225-kva/liebert-nx-225-kva_installation-manual_1008257022.webp)
Vertiv
™
|
Liebert
®
NX
™
225-600kVA Installation Manual | Rev. 8 | 07/2017
16
2.4.11
UPS Control Contacts with Global Maintenance Bypass
These contacts are used to communicate between the UPS module and Maintenance Bypass.
Use 14AWG cable wire up to 500ft. (150m).
Use 14AWG cable wire up to 500ft. (150m)
2.5
C
ONFIGURING
G
ROUND
C
ONNECTIONS
Liebert NX 225-600kVA is compatible with solidly grounded wye sources or a high resistance ground system, if
compatible. Refer to
2.5.3 - High-Resistance Ground Systems
.
Improper grounding is the largest single cause of UPS installation and startup problems. Grounding techniques
vary significantly from site to site, depending on several factors.
Proper grounding should be based on the appropriate NEC sections, but safe and proper equipment operation
requires further enhancements. The following pages detail recommendations for grounding various system
configurations to ensure optimal UPS system performance.
Table 5
Maintenance bypass key status
Terminal
Block
Pin
Description
TB3
5
Key status switch, closed = key inserted
6
Key status switch, common
7
Key status switch, closed = key removed
1.
See
2.6 - Distributed Static Switch (1+N) System Cabling Layouts
for 1+N systems with a Maintenance Bypass.
2.
Key Status Input must be Form-C contact
.
Table 6
Maintenance Bypass SKRU Enable
Terminal
Block
Pin
Description
TB4
1
Maintenance Bypass Cabinet, closed = load not on inverter
2
Maintenance Bypass Cabinet, common
3
Maintenance Bypass Cabinet, closed = load on inverter
1.
For 1+N systems with a maintenance Bypass, these contacts must be run to each module from an isolated source.
2.
These contacts must be run separately from all other control cables.
NOTE
Early production models may not be compatible with high-resistance ground systems.
!
CAUTION
The UPS ground lug must be solidly connected to the service entrance ground by an appropriately sized
wire conductor per the NEC.
Each conduit or raceway containing phase conductors must also contain a ground wire, both for UPS
input and output, which are solidly connected to the ground terminal at each termination point.
Conduit-based grounding systems tend to degrade over time. Therefore, using conduit as a grounding
conductor for UPS applications may degrade UPS performance and cause improper UPS operation.