Grounding diagram—Three-wire multi-module systems
2.5.2
Preferred Grounding Configuration, Battery Systems
Battery cabinet systems must be connected as floating (ungrounded) systems.
Center-tapped or grounded battery systems are not possible with battery cabinet systems.
Whether the battery system is open-rack or cabinet, the metal rack parts or cabinet must be grounded to the
UPS module ground bus.