MAINTENANCE
This chapter focuses on the UPS maintenance, including the battery and UPS cleaning.
6.1
Battery Maintenance
The battery cabinet uses a sealed, lead-acid, maintenance-free battery. Battery life depends on
the ambient temperature, charge and discharge times. High ambient temperatures shorten
battery life.
To prolong battery life:
•
Keep the ambient temperature from 15°C to 25°C
•
Prevent small current discharge.
•
Charge the battery for at least 12 hours, if the battery hasn't been charged for three months at specified
ambient temperature, or two months at high ambient temperature.
The waste lead-acid battery is dangerous waste material. Its storage, transportation, usage and
disposal must follow the national and local law and other criteria about the dangerous waste
material and the waste battery pollution prevention.
According to the related regulations, recycle the waste lead-aid battery; other disposal methods
are prohibited. Disposing of the waste lead-aid battery in a landfill or other waste dump can result
in serious environment pollution and violates national and local laws.
Vertiv has a service network and recycle system to assist users to deal with the waste battery by
law. Contact Vertiv Services at 800-543-2378 for information about recycling the waste battery.
6.2
Cleaning the UPS
Clean the UPS periodically, especially the ventilation holes, to ensure free airflow inside the UPS. If
necessary, clean the UPS with a vacuum cleaner or wipe with a dry cloth. Confirm that the
ventilation holes are unobstructed.
NOTE
Never perform maintenance while the UPS is on-line. Ensure that the UPS has been completely
powered Off when performing the UPS internal maintenance.
WARNING
Risk of electrical shock and high short circuit current. Can cause property damage, injury
and death
The following precautions must be observed before replacing the battery pack:
• Remove rings, watches and other metal objects.
• Use tools with insulated handles.
• Do not lay tools or other metal objects on the batteries.
• If the battery cabinet is damaged in any way or shows signs of leakage, contact your local
Vertiv representative immediately.
• Do not dispose of batteries in a fire. The batteries may explode.
• Handle, transport and recycle batteries in accordance with local regulations.
Содержание Liebert ITA2-08KRT208
Страница 1: ...Liebert ITA2 8 10kVA 60Hz 208 220V Three Phase UPS User Manual...
Страница 40: ...Vertiv Liebert ITA2 User Manual 34 Figure 31 Status page menus...
Страница 42: ...Vertiv Liebert ITA2 User Manual 36 Figure 34 Settings Page menus continued Monitor Pg 2 System Pg 2...
Страница 70: ...Vertiv Liebert ITA2 User Manual 64 NOTES...
Страница 71: ...Vertiv Liebert ITA2 User Manual 65...
Страница 72: ...Vertiv Liebert ITA2 User Manual 66...
Страница 73: ......