14
2.3
Installation Preparation
2.3.1
Location
For proper operation and to extend the UPS life, install the unit in an area with:
•
Convenient wiring
•
Adequate operator access area
•
Good ventilation
•
No corrosive gases
•
No excessive moisture
•
No excessive dust
•
Compliance with firefighting requirements
•
Operating temperature within the specifications shown in
2.3.2 Environmental Requirements
UPS Room
The UPS is designed for indoor installation in a clean, well-ventilated environment with the
ambient temperature within the specifications shown in
.
The internal fans provide forced air cooling for the UPS. Cooling air enters the UPS through the
front panel, and exhausts the hot air through the back. Maintain at least 8" (200mm) clearance in
the front and rear of the UPS (see
), to avoid obstructing the UPS ventilation and heat
dissipation.
Figure 9
Installation clearances
Wall
UPS
8"
(200mm)
Top view of rack