Vertiv
| Liebert
®
ITA2
™
User Manual |
43
Outpu
t
Voltage selection
208/220V
208V
Startup on bypass
Disable, Enable
Disable
Frequency selection
Auto, BypEna; Auto, BypDisa;
50Hz, BypDisa; 60Hz, BypDisa
Auto, BypEna
Inverter sync range
±0.5Hz, ±1.0Hz, ±2.0Hz, ±3.0Hz, ±4.0Hz,
±5.0Hz
±3.0Hz
Bypass voltage upper limit
+10%
Bypass voltage lower limit
-10%, -15%, -20%
default -10%
Bypass frequency range
±5Hz, ±10Hz
±10Hz
Run mode
Normal, ECO mode
Normal
ECO voltage range
±10%
±10%
Appear only
when 'Run
mode' is set to
'ECO mode'
ECO frequency range
±1Hz, ±2Hz, ±3Hz
±3Hz
ECO requalification time
5, 15, 30 (min)
5
Paralle
l
Voltage selection
208/220V
208V
Frequency selection
Auto, BypEna; Auto, BypDisa;
50Hz, BypDisa; 60Hz, BypDisa
Auto, BypEna
Run mode
Normal, ECO mode
Normal
Redundant
NO, YES
YES
System parallel No.
1~2
1
Sync parallel parameters
By HMI Interface Button
N/A
Batter
y
External battery cabinet group No.
Auto test, 0 ~ 10
Auto test
Low battery time
2 ~ 30 (min)
2
Battery replaced time
YYYY-MM-DD HH:MM:SS
2000-01-01 0:00:00
Battery test interval
Disable, 8 weeks, 12 weeks, 16 weeks, 20 weeks,
26 weeks
Disable
Battery test weekday
Sunday, Monday, Tuesday, Wednesday,
Thursday, Friday, Saturday
Wednesday
Battery test time
HH:MM:SS
0:00:00
Discharge protect time
1~4320 (min)
4320
Equal charge enable
NO, YES
NO
Temperature compensation
Disable, Enable
Disable
Replace battery
By HMI Interface Button
Button
Table 9
LCD parameter settings
(continued)
Menu
Item
Setting Range
Default Setting
Содержание Liebert ITA2-08KRT208
Страница 1: ...Liebert ITA2 8 10kVA 60Hz 208 220V Three Phase UPS User Manual...
Страница 40: ...Vertiv Liebert ITA2 User Manual 34 Figure 31 Status page menus...
Страница 42: ...Vertiv Liebert ITA2 User Manual 36 Figure 34 Settings Page menus continued Monitor Pg 2 System Pg 2...
Страница 70: ...Vertiv Liebert ITA2 User Manual 64 NOTES...
Страница 71: ...Vertiv Liebert ITA2 User Manual 65...
Страница 72: ...Vertiv Liebert ITA2 User Manual 66...
Страница 73: ......