Table 18
Liebert EXM MBC output currents
Voltage
3-Ph, 60Hz)
MBC
Rating,
kVA
System
Output
Current, A,
Max
Phase
Recommend
ed
Upstream
Protection,
A)
75°C Wire
Current A,
Total
Copper
Wire
Aluminum
Wire
Bolt Size
208/120
220/127
10
28
3W + N + G
40
50
(1) #6
(1) #4
M10
208/120
220/127
15
42
3W + N + G
60
85
(1) #4
(1) #2
M10
208/120
220/127
20
56
3W + N + G
70
115
(1) #2
(1) #2
M10
208/120
220/127
30
83
3W + N + G
110
130
(1) 1/0
(1) 2/0
M10
208/120
220/127
40
111
3W + N + G
150
175
(1) 3/0
(1) 4/0
M10
208/120
220/127
60
167
3W + N + G
225
285
(2)
300kcmil
(2) 2/0
M10
208/120
220/127
80
222
3W + N + G
300
400
(2) 3/0
(2) 4/0
M10
208/120
220/127
100
278
3W + N + G
350
460
(2) 4/0
(2)
300kcmil
M10
208/120
220/127
120
333
3W + N + G
450
620
(2) 350
(2) 500
M12
208/120
220/127
140
389
3W + N + G
500
620
(2) 350
(2) 500
M12
208/120
220/127
160
444
3W + N + G
600
760
(2) 500
(3) 350
M12
208/120
220/127
180
500
3W + N + G
700
930
(3) 350
(3) 500
M12
208/120
220/127
200
555
3W + N + G
700
930
(3) 350
(3) 500
M12
Table 19
Recommended lug sizes (compression type) M10, 3/8" bolt
Cable Size
T&B Copper
One Hole
T&B Aluminum
One Hole
#8AWG
54132
60104-TB
#6AWG
54136
60109
#4AWG
54140
60114
#2AWG
54143
60118
#1AWG
54148
60124
#1/0AWG
54109
60130
#2/0AWG
54110
60136
#3/0AWG
54111
60142
#4/0AWG
54112
60148
Содержание Liebert EXM MBC
Страница 1: ...Liebert EXM MBC User Manual 10 200kVA 208 120V and 220 127V 60Hz...
Страница 6: ...Vertiv Liebert EXM MBC Installation Manual iv...
Страница 51: ...Vertiv Liebert EXM MBC Installation Manual 45 NOTES...
Страница 52: ...Vertiv Liebert EXM MBC Installation Manual 46...
Страница 53: ......