MBC Installation Manual |
25
Figure 17 Outline drawing—800mm Liebert EXM MBC 160-200kVA system
Notes:
1. 24" (610mm) minimum clearance above unit for
air exhaust.
36" (914mm) front access required for service.
2. Keep cabinet within 15 degrees of vertical.
3. Top and bottom cable entry available through removable
access plates. Remove, punch to suit conduit size and replace.
4. Unit bottom is structurally adequate for forklift handling.
5. Control wiring must be run in separate conduits.
6. All wiring is to be in accordance with national and local
electrical codes.
7. The maintenance bypass cabinet will always be attached
to the UPS.
Leveler
Caster
DETAIL A
RIGHT SIDE
FRONT
78.7"
(2000mm)
34.3"
(872mm)
39.1" (993mm)
31.8" (808mm)
31.3" (800mm)
28.3"
(719mm)
Breakout
Centers
28.3"
(719mm)
22.8" (579mm)
Control Cable Entry
4.7" x 1.6"
(119mm x 41mm)
Control Cable Entry
5.9" x 2.0"
(150mm x 51mm)
BOTTOM VIEW
TOP
Ventilation
See DETAIL A
Power Cable Entry
26.8" x 16.8"
(681mm x 427mm)
Power Cable Entry
28.3" x 17.5"
(719mm x 445mm)
EXM12015
Rev. 1