Figure 14 Outline drawing—200mm Liebert EXM MBC, two to four breakers, 10-40kVA system
NOTES
1. 24" (610) minimum clearance above unit for air exhaust and
36" (914) front access required for service.
2. Keep cabinet within 15 degrees of vertical.
3. Top and bottom cable entry available through removable access plates.
Remove, punch to suit conduit size and replace.
4. Unit bottom is structurally adequate for forklift handling.
5. Control wiring and power wring must be run in separate conduits.
6. All wiring must be in accordance with national and local electrical codes.
7. Liebert EXM MBC will always be attached to the UPS; UPS shown for reference only.
8. Overall dimensions are shown with side panels.
Leveler
DETAIL A
TOP
BOTTOM
FRONT
UPS Shown for Reference Only
RIGHT SIDE
EXM12006
Pg. 1, Rev. 5
39.1" (993mm)
7.8" (200mm)
8.2"
(208mm)
Overall
78.7"
(2000mm)
See
Detail A
34.3"
(872mm)
4.7"
(119mm)
Ventilation
Control Cable
Entry 5.3" x 3.9"
(135 x 99mm)
Power Cable
Entry 5.3" x 7.3"
(135 x 185mm)
Power Cable
Entry 5.7" x 8.3"
(145 x 211mm)
16.1"
(408mm)
46"
(1168mm)
16.1"
(406mm)