41
Table 17
Liebert EXM MBC input currents, dual input, bypass
Voltage
3-Ph, 60
Hz
MBC
Rating
kVA
Bypass Input
Current
BIB/MBB
A, Max
Bypass
Recommended
Upstream
Protection, A
Phase
75°C Wire
Current
A Total
Copper
Wire
Aluminu
m
Wire
Bolt
Size
208/120
220/127
10
28
40
3W + N +
G
50
(1) #6
(1) #4
M10
208/120
220/127
15
42
60
3W + N +
G
85
(1) #4
(1) #2
M10
208/120
220/127
20
56
70
3W + N +
G
115
(1) #2
(1) #2
M10
208/120
220/127
30
83
110
3W + N +
G
130
(1) 1/0
(1) 2/0
M10
208/120
220/127
40
111
150
3W + N +
G
175
(1) 3/0
(1) 4/0
M10
208/120
220/127
60
167
225
3W + N +
G
285
(2) 300
(2) 2/0
M10
208/120
220/127
80
222
300
3W + N +
G
400
(2) 3/0
(2) 4/0
M10
208/120
220/127
100
278
350
3W + N +
G
460
(2) 4/0
(2) 300
M10
208/120
220/127
120
333
450
3W + N +
G
620
(2) 350
(2) 500
M12
208/120
220/127
140
389
500
3W + N +
G
620
(2) 350
(2) 500
M12
208/120
220/127
160
444
600
3W + N +
G
760
(2) 500
(3) 350
M12
208/120
220/127
180
500
700
3W + N +
G
930
(3) 350
(3) 500
M12
208/120
220/127
200
555
700
3W + N +
G
930
(3) 350
(3) 500
M12