Guide Specifications
3.21 DIGITAL SCROLL SENSOR FAILURE
The control shall monitor the status of the digital scroll sensor(s). If the control senses the
thermistor becomes disconnected, shorted or the reading goes out of range, the user will be notified
through an event on the local display and remote monitoring.
3.22 COMPRESSOR SEQUENCING
A user-selectable compressor sequencing parameter shall be provided and access through the local
control. This sequencing parameter presents the user with three choices:
•
Always use Compressor 1 as lead compressor.
•
Always use Compressor 2 as lead compressor.
•
Auto: The unit shall automatically stage compressors to keep each unit's run time within 8
hours of the other unit's run time. NOTE: The Auto setting attempts to maintain equal run
times between compressors. However, the control will not turn Off a compressor to equalize
run time when it is needed to control the space.
•
First priority
: If the safety timings are acceptable for only one compressor, that
compressor shall be the next to be started/stopped.
•
Second priority
: If both compressors are Off, the one with fewer working hours shall be
the next to start.
•
Third priority
: If both compressors are in operation, the one that has been operating
longer since the last start shall be the next to be stopped.
3.23 COMPRESSOR HIGH- AND LOW-TEMPERATURE LIMIT PROTECTION
The control shall monitor the return air to ensure that the compressor(s) are operated within the
manufacturer's defined window of operation. If the return air temperature deviates from the
manufacturer's window of operation, the Liebert iCOM shall automatically adjust to prevent
damage to the cooling unit or reduction in its reliability.
Содержание Liebert DSE
Страница 10: ...Vertiv Liebert DSE System Design and User Guide 10 This page intentionally left blank ...
Страница 15: ...Figure 2 2 Downflow bottom discharge blower configurations with EC fans 2 Nomenclature and Components 15 ...
Страница 16: ...Vertiv Liebert DSE System Design and User Guide 16 This page intentionally left blank ...
Страница 20: ...Vertiv Liebert DSE System Design and User Guide 20 This page intentionally left blank ...
Страница 22: ...Vertiv Liebert DSE System Design and User Guide 22 This page intentionally left blank ...
Страница 24: ...Vertiv Liebert DSE System Design and User Guide 24 This page intentionally left blank ...
Страница 32: ...Vertiv Liebert DSE System Design and User Guide 32 This page intentionally left blank ...
Страница 36: ...Vertiv Liebert DSE System Design and User Guide 36 This page intentionally left blank ...
Страница 46: ...Vertiv Liebert DSE System Design and User Guide 46 This page intentionally left blank ...
Страница 50: ...Vertiv Liebert DSE System Design and User Guide 50 This page intentionally left blank ...
Страница 52: ...Vertiv Liebert DSE System Design and User Guide 52 This page intentionally left blank ...
Страница 66: ...Vertiv Liebert DSE System Design and User Guide 66 This page intentionally left blank ...
Страница 68: ...Vertiv Liebert DSE System Design and User Guide 68 This page intentionally left blank ...
Страница 98: ...Appendix C Guide Specifications The following are the guide specifications for the Liebert DSE 69 ...
Страница 99: ...Vertiv Liebert DSE System Design and User Guide 70 This page intentionally left blank ...
Страница 119: ...Vertiv Liebert DSE System Design and User Guide ...