Guide Specifications
4.0 MISCELLANEOUS OPTIONS
4.1
HIGH-TEMPERATURE SENSOR—OPTIONAL
The high-temperature sensor shall be factory-installed in the unit and shall be factory-set to 125ºF
(52ºC). It shall immediately shut down the environmental control system when activated. The
sensor shall be mounted with the sensing element in the return air.
4.2
SMOKE SENSOR—OPTIONAL
The smoke sensor shall immediately shut down the Thermal Management system and activate the
alarm system when activated. The smoke sensor shall be mounted in the electrical panel with the
sensing element in the return air compartment. The smoke sensor is not intended to function as or
replace any room smoke detection system that may be required by local or national codes. The
smoke sensor shall include a supervision contact closure.
4.3
CONDENSATE PUMP, DUAL FLOAT—OPTIONAL
The condensate pump shall have a minimum capacity of 145 GPH (548 l/h) at 20 ft (58 kPa) head.
It shall be complete with integral dual-float switches, pump-and-motor assembly and reservoir. The
secondary float shall send a signal to the local alarm and shut down the unit upon high water
condition.
4.4
LOW VOLTAGE TERMINAL PACKAGE—OPTIONAL
Factory-installed and factory-wired terminals shall be provided.
•
Remote Shutdown Terminals
- 2 additional pairs of terminals provide the customer with
additional locations to remotely shut-down the unit by field-installed devices or controls.
•
Extra Common-Alarm Contacts
- 2 additional pairs of terminals provide the customer with
normally-open contacts for remote indication of unit alarms.
•
Main-Fan Auxiliary Switch
- 1 set of normally-open contacts wired to the EC-fan motor
contactor will close when EC-fan operation is required. This set of dry contacts could also be
used to initiate air economizer operation. Air economizer and associated devices by others.
•
Liqui-tect Shutdown
- 1 pair of dry contacts for the Liqui-tect sensor signal will provide unit
shut down. (Liqui-tect sensor is not included.)
4.5
REMOTE HUMIDIFIER CONTACT—OPTIONAL
A pair of N/O contacts provided for connection to a remote humidifier that allow the unit's
humidity controller to control a humidifier outside the unit. Power to operate the remote humidifier
does not come from the unit.
4.6
FAN OVERLOAD
The fan fault alarm is standard on all models.
4.7
COMPRESSOR OVERLOAD—STANDARD
A pair of N/O contacts shall be factory-installed and wired to each compressor to indicate
Compressor Overload.
Содержание Liebert DSE
Страница 10: ...Vertiv Liebert DSE System Design and User Guide 10 This page intentionally left blank ...
Страница 15: ...Figure 2 2 Downflow bottom discharge blower configurations with EC fans 2 Nomenclature and Components 15 ...
Страница 16: ...Vertiv Liebert DSE System Design and User Guide 16 This page intentionally left blank ...
Страница 20: ...Vertiv Liebert DSE System Design and User Guide 20 This page intentionally left blank ...
Страница 22: ...Vertiv Liebert DSE System Design and User Guide 22 This page intentionally left blank ...
Страница 24: ...Vertiv Liebert DSE System Design and User Guide 24 This page intentionally left blank ...
Страница 32: ...Vertiv Liebert DSE System Design and User Guide 32 This page intentionally left blank ...
Страница 36: ...Vertiv Liebert DSE System Design and User Guide 36 This page intentionally left blank ...
Страница 46: ...Vertiv Liebert DSE System Design and User Guide 46 This page intentionally left blank ...
Страница 50: ...Vertiv Liebert DSE System Design and User Guide 50 This page intentionally left blank ...
Страница 52: ...Vertiv Liebert DSE System Design and User Guide 52 This page intentionally left blank ...
Страница 66: ...Vertiv Liebert DSE System Design and User Guide 66 This page intentionally left blank ...
Страница 68: ...Vertiv Liebert DSE System Design and User Guide 68 This page intentionally left blank ...
Страница 98: ...Appendix C Guide Specifications The following are the guide specifications for the Liebert DSE 69 ...
Страница 99: ...Vertiv Liebert DSE System Design and User Guide 70 This page intentionally left blank ...
Страница 119: ...Vertiv Liebert DSE System Design and User Guide ...