Component
Subcomponent
Type
Event Name
ID
Latching
Definition
Board Name
—
Config Retrieval
Error
19
N
Board Name
EIB
Status
Communication
Fail
20
N
Communication has been lost to this board (HMI or Peripheral board
for DSPs) for 20 seconds. The HMI detects comm fails to the
monitoring boards and sends an event to each respective board once
comms are restored. A separate event is needed to show the Comms
Fail to the EIB at the system level especially when detected at PBM or
SFM (as opposed to every subfeed for example, like the BAM).
Board Name
—
Fault
FW Incompatible
21
N
Use by HMI. No logging. HMI sees a mismatch in configuration
schema or version number between HMI and monitor board.
Board Name
[BAM # or EIB if
applicable]
Alarm
Communication
Bus Error
22
N
The condition is when TX or RX stops for 10 seconds. The event is
detected at a board when the condition above occurs 5 times within a
24 hour sliding window. The event will clear when the occurrences are
3 or less in the 24 hour window.
Table 10.6 Common Events (continued)
10 Faults, Warnings and Events
75
Содержание Liebert DPM
Страница 1: ...Liebert DPM User Manual...
Страница 26: ...Vertiv User Manual 22 This page intentionally left blank...
Страница 30: ...Vertiv User Manual 26 This page intentionally left blank...
Страница 50: ...Vertiv User Manual 46 This page intentionally left blank...
Страница 61: ...Figure 7 10 Breaker Changes Completed 7 Add Remove and Configure Components 57...
Страница 62: ...Vertiv User Manual 58 This page intentionally left blank...
Страница 68: ...Vertiv User Manual 64 This page intentionally left blank...
Страница 71: ...ITEM DESCRIPTION 1 Context Menu 2 LIFESupport Contact Information 9 Vertiv Life Services 67...
Страница 72: ...Vertiv User Manual 68 This page intentionally left blank...
Страница 80: ...Vertiv User Manual 76 This page intentionally left blank...
Страница 81: ...Vertiv User Manual...