ITEM

DESCRIPTION

1

Arrow expands or closes Upper Meter options

2

BAR CONTROL SETUP indicates location in Touchscreen Control Panel

3

Upper Meter

4

Load Setting; cannot be changed

5

Threshold Sliders

6

Phase Meter

7

Current Setting; cannot be changed

8

Arrow expands or closes Phase Meter options

5.2.5 Settings - Unit

The Unit function on the Administrator's Context Menu permits changing several global settings, including:

Unit Name - unlimited characters, but all may not be displayed

Event Latching

Local EPO Enabled/Disabled

Remote EPO Enabled/Disabled

Frequency change (50 or 60 Hz)

Frequency Deviation Enabled/Disabled

Input Voltage Rating

System Voltage Rating

Overvoltage Fault Enabled/Disabled and Threshold

Undervoltage Fault Enabled/Disabled and Threshold

Many of the items have No/Yes boxes to choose from; touching either half of the box will switch the setting. Other items,
such as Frequency, have a drop-down menu. Touching others, such as Unit Name, activates a keypad to make changes.
Changes to any require touching the

Save

button to implement the change.

5.2.6 Settings - Import and Export

The Liebert® DPM permits Administrators to import or export settings from a system or from a configuration file written by
an offline DPM Configuration Editor application or exported and saved from another PDU. The offline application permits
creating common configuration files for multiple systems. This can save time when setting up duplicate systems or
reverting to a previous setup. The import and export functions are not available to Observers or Operators.

Export Settings

To export settings for a system:

1.

Log in as Administrator or Service.

2.

Connect a memory stick or an external drive to the USB port on the PDU or RPP.

3.

Touch Setup>Context Menu>Settings and select Export.

4. Name the

.INI

file to be exported.

5.

Touch the

Save

button.

Vertiv™ | User Manual

36

Содержание Liebert DPM

Страница 1: ...Liebert DPM User Manual...

Страница 2: ...ility for damages resulting from use of this information or for any errors or omissions Refer to other local practices or building codes as applicable for the correct methods tools and materials to be...

Страница 3: ...te Time and Time Zone 18 3 2 Change the Time Zone 18 3 3 Change the Date 19 3 4 Changing Date Time and Measurement Formats 19 3 4 1 Change the Date Format 19 3 4 2 Change the Time Format 19 3 4 3 Chan...

Страница 4: ...nfiguration One Line Diagram Links 49 7 2 Remove One Breaker from a Panelboard 50 7 3 Remove All Breakers from a Panelboard 52 7 4 Install Multiple Breakers 54 7 5 Change a Breaker 55 7 5 1 Add a Brea...

Страница 5: ...the top of the touchscreen summarizes system conditions with colors and an icon matched to the status The color and the icon change immediately if the system s status changes The right panel displays...

Страница 6: ...Warning or Alarm 6 Toolbar color coded for system status touching the status header will take you to the Events screen where any active events may be viewed and managed green indicates normal operatio...

Страница 7: ...Figure 1 2 System Status Toolbar Warning and Alarm Examples Figure 1 3 Liebert DPM Main Display Text View Operator Level Figure 1 4 Legend Graphical and Text Views 1 Introduction 3...

Страница 8: ...s can rename them Renaming permits site personnel to denote a component so that it s location and function are more readily apparent e g Rack Backup Servers There is no limit on the number of characte...

Страница 9: ...us on page 39 Determining when users logged in and out Context Menu Controls on page 27 Silencing alarms Reset Silence and Filter Faults and Events on page 59 Resetting faults Reset Silence and Filter...

Страница 10: ...level login The Liebert DPM has four access levels Observer Operator Administrator and Service each with different levels of authority The Observer level which does not permit configuration changes d...

Страница 11: ...ouch the OK button 6 Touch the Save button to keep your changes or touch the Cancel button to exit without saving NOTE To delete PIN requirements such as for a PDU or RPP in a secure area with restric...

Страница 12: ...gs unless the default view has been changed The appearance will differ only in the Context Menus displayed The Observer and Operator menus are the same but the Observer has view only access Context Me...

Страница 13: ...uchscreen Touch a lower level component to view details about it Components in the one line diagram signify their operational status by their color green white amber or red Faults Warnings and Events...

Страница 14: ...he display To customize the display s appearance 1 Log in to the Liebert DPM with Operator Administrator or Service Access if PINs are required 2 From the STATUS view touch the Context Menu icon in th...

Страница 15: ...more than one New View is created the Liebert DPM will number them in order of creation 3 Touch the Enter key on the on screen keyboard after entering the new name 4 Select the number of panels in th...

Страница 16: ...Figure 2 7 Create a Panel Layout ITEM DESCRIPTION 1 Name for newlayout 2 Number of panels in newlayout 3 Content links for panels in newlayout 4 Location of panels in newlayout Vertiv User Manual 12...

Страница 17: ...ghlighted may be edited or removed 2 4 Using the Edit Icon to Customize Layout The Touchscreen Control Panel layout can also be changed with the Edit icons on the screen The Edit icon can be used to a...

Страница 18: ...r push a handle to resize the panel this is possible only if the panel shares half the Touchscreen Display with another panel see Figure 2 9 on the facing page 8 Move a Panel Touching and holding the...

Страница 19: ...will be acceptable for most applications but it can be changed to a blue background or a light gray background accompanied by changes to the dialog boxes and text Users at any access level Observer O...

Страница 20: ...Figure 2 10 Choose a Theme Figure 2 11 Themes Light_Gray_9 and Blue_9 item DESCRIPTION 1 Light_Gray_9 theme 2 Blue_9 theme Vertiv User Manual 16...

Страница 21: ...n interaction Choices are 1 minute 2 minutes 3 minutes 4 minutes 5 minutes 10 minutes and 15 minutes Display Brightness The default setting is 80 percent but the brightness may be changed in increment...

Страница 22: ...splay Options Formats refer to Changing Date Time and Measurement Formats on page 19 The control will display local time and UTC Time in the STATUS Context Menu Display Options Date Time view The cont...

Страница 23: ...IME page 6 Touch the Save button to make the changes or touch Cancel to exit without saving the changes NOTE Touching the Graphic Text icon permits changing the date by scrolling though months days an...

Страница 24: ...OM LABELS page permits renaming settings serial ports and network interfaces New names may be entered for these to suit local preferences and to ease troubleshooting and refine data The default name o...

Страница 25: ...5 Touch the Enter key 6 Touch Save to make the change or touch Cancel to exit without saving Figure 3 2 Create or Modify Custom Labels 3 Setting Display Properties 21...

Страница 26: ...Vertiv User Manual 22 This page intentionally left blank...

Страница 27: ...t these PINs may be changed from the factory set numbers NOTE Vertiv recommends recording any PINs set and storing the numbers where they are accessible if they are forgotten A user with authority to...

Страница 28: ...s Administrator or higher 2 Touch SETUP at the top of the screen 3 Touch the Role whose PIN will be set or changed 4 Touch the PIN value on the right side of the Touchscreen Control Panel 5 Enter a PI...

Страница 29: ...t PIN shown after touching PIN Value 3 Log Out icon 4 Save button 5 OK button 6 Enter button 7 Keypad NOTE Vertiv recommends keeping a current list of PINs in a location known to administrative person...

Страница 30: ...Vertiv User Manual 26 This page intentionally left blank...

Страница 31: ...t menu seen by an Observer appears identical to the Context Menu seen by an Operator However when an Operator or Administrator is logged in the Context Menu permits actions such as customizing the lay...

Страница 32: ...displays an ellipsis Clicking on that row will create a double row displaying the full component or subcomponent name Metering View only system components voltage current power usage and peak current...

Страница 33: ...options for all access levels Observers can export the log as a CSV file for recordkeeping analysis and similar uses If a component or subcomponent name is too long the Liebert DPM displays an ellipsi...

Страница 34: ...nfigured capacity model number and serial number 5 2 1 View or Change Network Settings Because the Liebert DPM monitors and manages the PDU or RPP over a network the Liebert DPM restricts communicatio...

Страница 35: ...Figure 5 2 Change Network Settings Ethernet ITEM DESCRIPTION 1 Ethernet network selected 2 Enabled Disabled choice 3 IP address source DHCP or Static 5 Context Menu Controls 31...

Страница 36: ...nput Contact s delay current may also be adjusted To change the Input Contact settings 1 Log in with Administrator or Service access 2 Touch SETUP Context Menu Input Contact 3 Select an external input...

Страница 37: ...ITEM DESCRIPTION 1 Context Menu location 2 Default contact name 3 Contact String default changing from Preset to Custom enables specifying and renaming the string 4 Custom or Preset type of contact 5...

Страница 38: ...he name on the left side of the Touchscreen Control Panel 4 Touch the Assigned Event dialog box to select an event and assign it to the contact 5 Touch the Save button to keep your change or touch the...

Страница 39: ...ouch the plus or minus sign at the ends of the slider to increase or decrease the threshold value The threshold determines when the Liebert DPM changes the Status Bar color and icon 4 Touch the Save b...

Страница 40: ...lf of the box will switch the setting Other items such as Frequency have a drop down menu Touching others such as Unit Name activates a keypad to make changes Changes to any require touching the Save...

Страница 41: ...e imported to the USB port on the PDU or RPP 3 Touch Setup Context Menu Settings and select Import 4 Select the INI file to be imported 5 Select the import method to use Full Settings Partial Settings...

Страница 42: ...file ITEM DESCRIPTION 1 Context Menu Choose Settings Import to import an INI file 2 Setup 3 Import button Touch this after selecting the file to import 4 Select Import file Choose the INI file to impo...

Страница 43: ...iled information touch Transformer at the top of the one line diagram The Liebert DPM opens to the TRANSFORMER screen at Meter Data This displays metered values for each phase see Figure 6 1 below Fig...

Страница 44: ...numerically text for the entire panelboard The thresholds for the warning fault color are the overcurrent warning fault thresholds for the panelboard To view a Panelboard s Summary Status 1 Touch Sta...

Страница 45: ...iewed 2 Panelboard main 3 Summary tab 4 Panelboard branch breakers Figure 6 3 Panelboard summary status Fault ITEM DESCRIPTION 1 Panelboard being viewed 2 Panelboard main 3 Summary tab 4 Panelboard br...

Страница 46: ...e panelboard in the one line diagram This displays a one line diagram of the panelboard s components each color coded to show its status 2 Touch Meter Data This displays the view shown in Figure 6 4 b...

Страница 47: ...n touch the subfeed in the one line diagram This displays a one line diagram of the subfeed depending on touchscreen space and the Meter Data screen for the subfeed as shown in Figure 6 5 below Figure...

Страница 48: ...akers 3 Value to be reset same text appears with all reset screens but value being reset may be kWH Peak Demand or Peak Current 6 2 3 Reset Peak Demand Touching the Reset Peak Demand button displays a...

Страница 49: ...ge 44 These settings may be used to track power consumption by particular equipment 6 2 5 View Transformer Configuration The system s overall configuration may be viewed by touching STATUS Transformer...

Страница 50: ...Vertiv User Manual 46 This page intentionally left blank...

Страница 51: ...permit Observers and Operators to view the system its components and warning and fault settings These two user classes cannot however alter settings Using the Context Menu permits additional changes...

Страница 52: ...n inactive until change is made 7 Clear Panel button removes all breakers from panel Additional settings not shown in Figure 7 1 above which may be viewed by scrolling down are Neutral Overcurrent Ena...

Страница 53: ...ker Configuration One Line Diagram Links To change a breaker s configuration with one line diagram links 1 Log in with Administrator access if PINs are required 2 Touch STATUS and select the panelboar...

Страница 54: ...ing either the plus or minus sign once will increase or decrease the threshold value by one percentage point b Holding either the plus sign or minus sign will move the threshold indicator continuously...

Страница 55: ...Figure 7 3 Select Breaker to be Deleted ITEM DESCRIPTION 1 Selected breaker 2 Configuration tab chosen signified by white bar underneath 3 Delete button 7 Add Remove and Configure Components 51...

Страница 56: ...a panelboard is replaced with a panelboard that has a different arrangement of breakers This function is not possible at the Observer or Operator access level To remove all breakers 1 Log in with Admi...

Страница 57: ...ections 2 Add breaker icon 3 Configuration tab 4 Save button inactive until change is made 5 Cancel button inactive until change is made 6 Clear Panel button not visible to Observers or Operators Figu...

Страница 58: ...box all available breaker positions will be selected in green and labeled New Breaker 4 Touch the Next button 5 At the next screen enter the breaker rating on the keypad and touch the Done box NOTE T...

Страница 59: ...n open section of a panelboard 1 Log in at the Administrator or Service level if PINs are required 2 Touch the panelboard with the breaker s to be altered If you are installing a new breaker continue...

Страница 60: ...itions are open 6 Touch the Next button The ADD BREAKER DETAILS window opens 7 5 2 Set Breaker Details 7 Set the breaker rating enable or disable Overcurrent Fault the fault threshold and enable or di...

Страница 61: ...Figure 7 10 Breaker Changes Completed 7 Add Remove and Configure Components 57...

Страница 62: ...Vertiv User Manual 58 This page intentionally left blank...

Страница 63: ...vents that have occurred over time assessing system performance under various conditions and modes of operation The Event Log does not permit resetting or silencing events The Event Log may be exporte...

Страница 64: ...a warning a green shield with a check mark is normal operation 5 Event ID 6 Component that the event affected 7 Arrowhead denotes which heading was used to sort the active EVENTS list Component in th...

Страница 65: ...er button This displays the Event Filter list 3 Select the parameter used to filter the list either Severity Filters Status Alarm and Fault or Component Filters populated with the current list of comp...

Страница 66: ...filtering events enabling users to view only certain events To filter events and faults 1 Touch Status Context Menu Logs Event Log This displays the Event Log 2 Touch the Filter button 3 Select the p...

Страница 67: ...Figure 8 4 Filter Events Event Log Scrolling will permit viewing components not shown in the example above 8 Reset Silence and Filter Faults and Events 63...

Страница 68: ...Vertiv User Manual 64 This page intentionally left blank...

Страница 69: ...time and operational efficiency through continuous monitoring expert analysis and proactive response Detailed parametric data is continuously captured with advanced technology embedded in select crit...

Страница 70: ...Figure 9 2 Vertiv LIFE Services Contact From LIFE SERVICES Icon Figure 9 3 Vertiv LIFE Services Contact From Context Menu Vertiv User Manual 66...

Страница 71: ...ITEM DESCRIPTION 1 Context Menu 2 LIFESupport Contact Information 9 Vertiv Life Services 67...

Страница 72: ...Vertiv User Manual 68 This page intentionally left blank...

Страница 73: ...el Input 1 Fault Invalid Phase Rotation 110 The input phases are not in the normal A B C sequence Input 1 Fault Phase Loss 111 The input phase voltages are unbalance by 20 and all voltages are greater...

Страница 74: ...t phases are not in the normal A B C sequence Input 2 Fault Phase Loss 134 The input phase voltages are unbalance by 20 and all voltages are greater than 50v Input 2 Fault High Voltage THD 135 One of...

Страница 75: ...ses are belowthe setpoint for the set period PBM Mains Label Breaker Label Status Energy Measure Rollover 235 The kWH Total measurement has exceeded its maximum value Parametric data 1 indicates panel...

Страница 76: ...e I rms phases has exceeded the warning setpoint for the set period SFM Panel Name Subfeed Label Fault Neutral Overcurrent 334 L The In rms has exceeded the alarm setpoint for the set period SFM Panel...

Страница 77: ...m compatible Table 10 4 HMI User Events Component Subcomponent Type Event Name ID Latching Definition Board Name EIB Alarm Internal Input Contact 1 600 L Internal alarm is active Default text High Tem...

Страница 78: ...el A 2 Panel B Branch N0 0 Mains 1 to 84 Branch No 0xFF Mains and Branch on this panel Parametric Data Examples XFM 0 0 0 PBM 1 or 2 panel 0xff All branches 0 PBM 1 or 2 panel 0 to 84 branch 0 SFM I L...

Страница 79: ...tem level especially when detected at PBM or SFM as opposed to every subfeed for example like the BAM Board Name Fault FW Incompatible 21 N Use by HMI No logging HMI sees a mismatch in configuration s...

Страница 80: ...Vertiv User Manual 76 This page intentionally left blank...

Страница 81: ...Vertiv User Manual...

Страница 82: ...names and logos referred to are trade names trademarks or registered trademarks of their respective owners While every precaution has been taken to ensure accuracy and completeness herein Vertiv Group...

Отзывы: