Note: Before connecting the control line, it is mandatory to perform the corresponding anti-static measures.
2.4.4. Connecting Belt Type Leak Detector
Each unit is equipped with a 10m long belt type water leakage detector, and the water leakage detection transmitter has
been installed in the electric box of the lower section. Only need to arrange the belt type water leakage detector in the
corresponding position on site, and then connect it with the water leakage detector transmitter.
2.4.5. Remote Shutdown Control Line Connection
, 37# and 38# terminals can connect to remote shutdown switch, and they have been shorted in the
factory and the shorting cable should be removed if the terminals are to be connected to the remote shutdown switch.
Figure 2-24 Remote Shutdown
Note: When 37# and 38# are opened, the unit will shut down.
2.4.6. Common Alarm
Terminals 75# and 76# can be connected to the common alarms. The output signals to external alarm devices, such as alarm
indicators. When a critical alarm occurs, the contact will be closed to trigger remote alarms, send signals to the building
management system or dial the paging system automatically. The power supply of the external general alarm system is user
prepared.