Vertiv™ | Liebert® AHU | User Manual
51
EC fan cannot be
started
EC fan failure
If the EC fan fault alarm triggers and restarts automatically then the
possible reasons are as follows:
1. EC fan is blocked
2. EC fan is out of phase
3. EC Fan internal communication master slave error
4. EC fan is under voltage
If the EC fan is automatically restarted but there is still EC fan fault
alarm, then the reasons are as follows:
1. EC fan is reversed
2. The bus voltage is high
3. The power supply harmonic distortion rate is high (THDU>10%).
4. To determine the specific reasons: Connect to 485 communication
port and use the EBM manufacturers software for analysis.