8.
For an internal fan, perform the following steps. Save all hardware for re-use.
Remove the top (3) and bottom (3) sets of bolts and lock washers from the fan outer mounting plate. Refer to Figure
17.4.
Carefully slide the fan outer mounting plate with fans attached out far enough to disconnect the fan connectors.
Set the fan outer mounting plate with fans attached on a suitable work surface.
Remove the defective fan with inner mounting plate attached from the fan outer mounting plate by removing the (4)
sets of nuts and lock washers. Refer to Figure 17.4.
Figure 17.4
Removing the Fan Outer Mounting Plate
Fan Outer
Mounting Plate
Outside of Door with
Shrouds Removed
Fan Outer
Mounting Plate
(6 sets per mounting plate)
- No. 8 Flat Washer
- 8-32 Lock Nut
(8) Sets (4 sets per fan)
- 1/4-20 x 0.75 Machine Screws
- No. 10 Flat Washers
- M5 Hex Nuts