25
Configurable output dry
contact 1 (Normally
Open) J7-25/27
Configurable input dry
contact 1:
0) Undefined
1) System alarm
2) On battery
3) UPS power supply (default)
4) Mains input abnormal
5) On bypass
6) Battery low capacity
7) Remote EPO
8) UPS fault
9) On maintenance bypass
10) UPS is ready
11) Battery off J7-25/27
shorted to execute the above
status
26
Configurable output
dry contact 2
(Normally Open) J7-
26/28
Configurable input dry contact 2:
0) Undefined
1) System alarm
2) On battery
3) UPS power supply (default)
4) Mains input abnormal
5) On bypass
6) Battery low capacity
7) Remote EPO
8) UPS fault
9) On maintenance bypass
10) UPS is ready
11) Battery off J7-26/28 shorted to
execute the above status
27
Configurable output dry
contact 1 (Common)
J7-25/27
28
Configurable output
dry contact 2
(Common) J7-26/28
29
Configurable output dry
contact 3 (Normally
Open) J7-29/31
Configurable input dry
contact 3:
0) Undefined
1) System alarm
2) On battery
3) UPS power supply (default)
4) Mains input abnormal
5) On bypass
6) Battery low capacity
7) Remote EPO
8) UPS fault
9) On maintenance bypass
10) UPS is ready
11) Battery off J7-29/31
shorted to execute the above
status
30
Configurable output
dry contact 2
(Normally Open) J7-
30/32
Configurable input dry contact 2:
0) Undefined
1) System alarm
2) On battery
3) UPS power supply (default)
4) Mains input abnormal
5) On bypass
6) Battery low capacity
7) Remote EPO
8) UPS fault
9) On maintenance bypass
10) UPS is ready
11) Battery off J7-30/32 shorted to
execute the above status
31
Configurable output dry
contact 3 (Common)
J7-29/31
32
Configurable output
dry contact 2
(Common) J7-30/32
T able 4.6 Descriptio n o f dry co n tact po rt J 7 (co n tin u ed)
N O T E:
1. T h e pro gram m able dry co n tact sh o u ld be co n figu red via P aram set.
2. In parallel system , th e dry co n tacts o f th e extern al m ain ten an ce iso latio n circu it break er sh all
be co n n ected to th e co rrespo n din g dry co n tacts o f each rack .
4 Electrical Installation
46
Vertiv™ Liebert® APM Plus User Manual
Содержание APM 0250kMK16FN02000
Страница 1: ...Vertiv Liebert APM Plus User Manual 50 250 kVA UPS...
Страница 8: ...vi This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Страница 16: ...1 Important Safety Instructions 8 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Страница 30: ...2 Overview 22 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Страница 60: ...4 Electrical Installation 52 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Страница 73: ...Figure 5 11 Customize the display 5 Operator Control and Display Panel 65 Vertiv Liebert APM Plus User Manual...
Страница 97: ...5 Operator Control and Display Panel 89 Vertiv Liebert APM Plus User Manual...
Страница 154: ...Figure 8 8 LBS port J4 on bypass control module 8 Parallel System and LBS System 146 Vertiv Liebert APM Plus User Manual...
Страница 182: ...11 Service and Maintenance 174 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Страница 188: ...12 Specifications 180 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Страница 191: ...Vertiv Liebert APM Plus User Manual...