6.7 UPS Reset Procedures after EPO
After shutting down the UPS through EPO or reasons of UPS fault, clear the fault according to the alarm message displayed
on TOUCH SCREEN screen. Then carry out the following reset procedures to make UPS resume normal operation.
After confirming the fault has been cleared and no remote EPO signal is received, the user can carry out the following
procedures:
1.
Click the Reset FAULT button (Refer to Operator Controls), the system will exit the EPO/abnormal OFF state,
and the alarm indicator flashes in red color.
2.
After the rectifier start-up is finished, normally start the UPS according to Transfer from Normal Mode to
Bypass Mode.
N O T E: T h e rectifier will start au to m atically wh en th e o vertem peratu re fau lt disappears five m in u tes
after th e disappearan ce o f o vertem peratu re sign al.
3.
After pressing the EPO button, if the mains input is switched off, the UPS will shut down completely. When the
mains input returns, the UPS will start up on bypass. There will be power at the output terminals of the UPS.
W A R N IN G ! If th e m ain ten an ce bypass switch Q 3 is clo sed, an d UP S h as in pu t po wer, it m ean s
UP S h as o u tpu ts.
6.8 Automatic Restart
In the case of a mains failure, the UPS draws power from the battery system to supply the load until the batteries are
depleted. When the UPS reaches its EOD threshold, it will shut down.
The UPS will automatically restart and enable output power only when the following conditions are met:
1.
If Auto Recovery after EOD is enabled.
2.
After the Auto Recovery after EOD Delay Time expires (the default delay is 10 minutes), the UPS restarts
bypass, then inverter. During the automatic recovery delay, the UPS will charge its batteries to provide a safety
margin for equipment shutdown if input power fails again.
N O T E: Du rin g th e au to m atic restart pro cess, m an u al startu p is disabled. A u to m atic restart m u st be set
by Vertiv's au th o rized service en gin eer th ro u gh Vertiv settin g so ftware.
6 Single UPS Operation Introduction
115
Vertiv™ Liebert® APM Plus User Manual
Содержание APM 0250kMK16FN02000
Страница 1: ...Vertiv Liebert APM Plus User Manual 50 250 kVA UPS...
Страница 8: ...vi This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Страница 16: ...1 Important Safety Instructions 8 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Страница 30: ...2 Overview 22 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Страница 60: ...4 Electrical Installation 52 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Страница 73: ...Figure 5 11 Customize the display 5 Operator Control and Display Panel 65 Vertiv Liebert APM Plus User Manual...
Страница 97: ...5 Operator Control and Display Panel 89 Vertiv Liebert APM Plus User Manual...
Страница 154: ...Figure 8 8 LBS port J4 on bypass control module 8 Parallel System and LBS System 146 Vertiv Liebert APM Plus User Manual...
Страница 182: ...11 Service and Maintenance 174 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Страница 188: ...12 Specifications 180 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Страница 191: ...Vertiv Liebert APM Plus User Manual...