The IMPORTANT Configuration File Editor
4200-002
33
Revision 6
Threshold Tab
– Configuration Editor
Data in the
Threshold tab
configures the
Cellcorder unit.
Use the Threshold
tab to set low and
high limits for
voltage, resistance,
temperature, and
SG.
Select the
Temperature Unit
in C for Celsius or
F for Fahrenheit.
Figure 64. Threshold Tab
NOTES:
Threshold levels cannot be set to zero.
During testing, two beeps on the Cellcorder indicate limits
are exceeded.
The Threshold Tab is not used for changing the display
colors or threshold levels in the BAS program.
The Temperature Unit function, C or F is used for CRT
setup and does not convert temperatures from F to C or C
to F.