CLC-200
4200-002
183
Revision 6
Figure 375. Cellcorder CLC–200 Data Capture
In the
Battery Number
box, select which battery data to
download from the Cellcorder. If the Memory Mode is 7 x 256,
the selection is from one to seven. If 28 x 64, the selection is
from one to 28.
Download the First nn Cells
defaults to the Number of Cells on
the File|Properties|General tab. It is the maximum number of
cells from which data will be captured and usually matches the
number of cells in the battery.
Set
... at Cell Number nn
to the cell number the CLC should
start downloading data to, typically one. Thus, Cellcorder Cell 1
data is recorded in the file under Cell 1, and so on.
NOTE:
Change the starting cell number when more than one
Cellcorder records data from the same battery. For
example, on a 256
–cell battery, one Cellcorder tests cells 1
to 128 and stores the data in Cellcorder locations 1 to 128.
The other Cellcorder tests cells 129 to 256 and stores in 1
to 128 as well. Capture the first Cellcorder with the starting
cell number set to one and capture the second into the
same file with the starting number set to 129.
Set the
Read Date for this Data Set
. Type a date or click the
drop–down button and use the calendar.
To start capturing data, click OK. A bar on the Interface box
indicates progress. When finished, status shows Download 100%
completed (
nn
Cells). Click OK.
Содержание Alber Cellcorder CRT-400
Страница 1: ...Cellcorder Battery Analysis System User s Guide 590 2085 501A SL 29400 4200 002_Rev6 ...
Страница 17: ...4200 002 xvii Revision 6 Figure 374 CLC 200 Interface 182 Figure 375 Cellcorder CLC 200 Data Capture 183 ...
Страница 18: ......
Страница 47: ...The IMPORTANT Configuration File Editor 4200 002 29 Revision 6 Figure 58 BLF On The Website ...
Страница 167: ...Generating Reports Five Report Types 4200 002 149 Revision 6 Figure 301 Data Set Detail Report Examples ...
Страница 174: ...Generating Reports Five Report Types 4200 002 156 Revision 6 Figure 316 Threshold Report With Graphs Example ...