Specific Methods Of Creating ADFs
4200-002
87
Revision 6
The Hydrometer
Interface window
appears.
Set ...Starting at Cell
Number nn to the cell
number the hydrometer
should start
downloading data to,
typically 1. Thus,
hydrometer Cell 1 data
is recorded in the file
under Cell 1, and so on.
Figure 174. Hydrometer Interface
NOTE:
Change the starting cell number when more than one
hydrometer records data from the same battery. For
example, on a 256
–cell battery, one hydrometer tests cells
1 to 128 and stores the data in hydrometer locations 1 to
128. The other hydrometer tests cells 129 to 256 and stores
in 1 to 128 as well. Capture the first hydrometer's data with
the starting cell number set to one and capture the second
hydrometer's data into the same file with the starting
number set to 129.
Set the
Read Date for this Data Set
. Type a date or click the
drop–down calendar button.
Set the
Temperature Unit in Hydrometer
box to C or F to
agree with how hydrometer temperature readings were made.
CAUTION:
This setting does not convert the readings from C to F or
from F to C.
To start capturing, click
.
The progress bar moves and the Interface box shows
Receiving data
for cell number
. When done, the message
The hydrometer has
successfully downloaded n cells
appears.
Содержание Alber Cellcorder CRT-400
Страница 1: ...Cellcorder Battery Analysis System User s Guide 590 2085 501A SL 29400 4200 002_Rev6 ...
Страница 17: ...4200 002 xvii Revision 6 Figure 374 CLC 200 Interface 182 Figure 375 Cellcorder CLC 200 Data Capture 183 ...
Страница 18: ......
Страница 47: ...The IMPORTANT Configuration File Editor 4200 002 29 Revision 6 Figure 58 BLF On The Website ...
Страница 167: ...Generating Reports Five Report Types 4200 002 149 Revision 6 Figure 301 Data Set Detail Report Examples ...
Страница 174: ...Generating Reports Five Report Types 4200 002 156 Revision 6 Figure 316 Threshold Report With Graphs Example ...