Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
3
2
Installing the System
2.1
General Requirements
•
The shelf is designed for mounting in a 19-inch or 23-inch wide relay rack with 1-3/4 inch multiple drilling.
•
The installer should be familiar with the installation requirements and techniques to be used in securing the shelf(s) to a relay
rack.
•
This product is intended only for installation in a Restricted Access Location on or above a non-combustible surface.
•
This product must be located in a Controlled Environment with access to Craftspersons only.
•
This product is intended for installation in Network Telecommunication Facilities (CO, vault, hut, or other environmentally
controlled electronic equipment enclosure).
•
This product is intended to be connected to the common bonding network in a Network Telecommunication Facility (CO,
vault, hut, or other environmentally controlled electronic equipment enclosure).
•
Typical industry standards recommend minimum aisle space clearance of 2'6" for the front of the relay rack and 2' for the rear
of the relay rack.
•
Converter module and mounting shelf ventilating openings must not be blocked and temperature of air entering system must
not exceed rated Operating Ambient Temperature Range found in SAG584622100.