Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
6
2.4
Securing the Expansion Shelf(s) to a Relay Rack and Installing the
Expansion Wiring Cover on the Main Shelf
Securing an Expansion Shelf to a Relay Rack
Secure an expansion shelf to a relay rack, directly below the shelf above it, per the previous procedure. The optional 1U wiring access
panel is recommended for expansion shelves to facilitate load cable connections.
Installing the Expansion Wiring Cover on the Main Shelf
Procedure
1.
Remove the cover shown in Figure 2.3 from the main shelf.
2.
Remove the expansion wiring cover from the expansion shelf as shown in Figure 2.3.
3.
On the expansion wiring cover for both the expansion shelf and the main shelf (provided loose with the expansion shelf),
remove the tabs shown in Figure 2.3 so wiring can pass between the shelves. Apply the provided material along the exposed
edges of the cutouts to provide protection to the wires as they are passed between shelves.
4.
Make the paralleling connections as described in the “
Making Electrical Connections
” section of this document.
5.
Refer to Figure 2.3, and install the expansion wiring covers to both the main shelf and the expansion shelf.
Figure 2.3: Installing the Expansion Wiring Cover on the Main Shelf
Expansion Wiring Cover
(supplied loose with Expansion
Shelf, attach to Main Shelf)
Replace this cover with the
Expansion Wiring Cover
Remove these tabs at the bottom of the top shelf and
at the top of the bottom shelf to allow wiring between
shelves.
Apply the provided material along the exposed edges
of the cutouts to provide protection to the wires as they
are passed between shelves.
584622100 / 584622200 shown.
584622300 / 584622400 similar.