Vertiv
|
eSure™ Power Extend Converter Installation and User Manual (UM565050)
|
Rev. D
25
WARNING!
The power extend converter and front mounting bracket
becomes very hot during power extend converter operation at heavy
load. Wear heat resistant gloves or allow the power extend converter
to cool down before removing.
Refer to the instructions furnished with the mounting bracket kits for
complete installation instructions. The following is a typical installation
procedure.
Typical Installation Procedure
DANGER!
Adhere to the “Important Safety Instructions” starting on
page 6 and those listed in the power system manual.
ALERT!
Only install the power extend converter into a -48 VDC
distribution position.
NOTE!
Mounting bracket kit P/N 565391 with distribution panel
582127000 List AA is used in the following procedure. Other kits and
distribution panels similar. For complete installation instructions,
refer to the instructions furnished with the mounting bracket kits.
[ ] 1.
Performing this procedure may activate external alarms. Initial
installation of the converter with the switch in the off position will
actuate the CB/Fuse Alarm. Do one of the following. If possible,
disable these alarms. If these alarms cannot be easily disabled,
notify the appropriate personnel to disregard any future alarms
associated with this system while the procedure is being
performed.
[ ] 2.
Gain access to the distribution panel into which the power
extend converter is to be installed.
[ ] 3.
Install the power extend converter mounting bracket kit per the
installation instructions furnished with the kit. If two or three
power extend converters are to be connected in parallel, a
two-position (60016097) or three-position (545346) lug adapter
busbar plate should be installed first, as shown in the separate kit
installation instructions.
[ ] 4.
If the power extend converter is to be installed for a newly
connected load, connect the load and load return cables to the