Vertiv
|
eSure™ Power Extend Converter Installation and User Manual (UM565050)
|
Rev. D
24
9.
Local Status and Alarm Indicator: An LED indicator is provided on
the front of the power extend converter to provide visual operating
status or failure condition of the power extend converter. Refer to
Mechanical Specifications
1.
Weight: 0.45 kg (1.0 lb).
2.
Dimensions (H x W x D) (body): 4.35” (110.49 mm) x 0.73” (18.54
mm) x 4.64” (117.87 mm).
INSTALLATION
General Requirements
•
This product is intended only for installation in a restricted access
location on or above a non-combustible surface.
•
This product must be located in a controlled environment with
access to Crafts persons only.
•
This product is intended for installation in network
telecommunication facilities (CO, vault, hut, or other environmentally
controlled electronic equipment enclosure).
•
This product is intended for connection to the common bonding
network in a network telecommunication facility (CO, vault, hut, or
other environmentally controlled electronic equipment enclosure).
•
The DC return connection to this system can remain isolated from
system frame and chassis (DC-I).
•
This system is suitable for installation as part of the Common
Bonding Network (CBN).
Installing the Power Extend Converter
NOTE!
The power extend converter can be inserted or removed with
power applied (hot swappable) as long as the power extend
converter is inserted/removed with the enable/disable switch in the
disabled position. See
on page 34.