Vertiv
|
eSure™ Power Extend Converter Installation and User Manual (UM565050)
|
Rev. D
20
internal input fault protection device(s). No damage to connection
points when inserted into a live bus.
5.
Typical Input Data: See
Table 6:
Typical Input Data
Vin (VDC) % load
Iin (ADC) Vo (VDC) Io (ADC)
Eff
Wloss (W) BTU/hour
42
42.04
0
0.04
58.27
0.00
na
1.68
5.74
42.03
25.16%
6.22
58.11
4.33
0.9625
9.81
33.47
42.08
49.96%
12.22
57.96
8.62
0.9716
14.60
49.83
42.02
75.13%
18.33
57.79
13.00
0.9754
18.96
64.68
42.02
100.09%
24.42
57.62
17.37
0.9754
25.27
86.22
48
48.1
0.00%
0.07
58.29
0.00
0.00
3.37
11.49
48.19
20.24%
4.34
58.16
3.48
0.9677
6.75
23.02
48.15
30.55%
6.52
58.08
5.26
0.9731
8.44
28.79
47.99
50.01%
10.65
57.95
8.63
0.9785
10.99
37.48
48
70.84%
15.05
57.83
12.25
0.9806
13.98
47.71
47.96
80.81%
17.18
57.76
13.99
0.9807
15.89
54.22
48.01
99.89%
21.21
57.64
17.33
0.9810
19.39
66.16
54.5
54.44
0.00%
0.08
58.27
0.00
0.00
4.36
14.86
54.59
20.35%
3.82
58.13
3.50
0.9756
5.08
17.33
54.47
30.43%
5.70
58.07
5.24
0.9801
6.19
21.13
54.51
50.03%
9.32
57.97
8.63
0.9847
7.78
26.55
54.54
70.70%
13.15
57.81
12.23
0.9858
10.18
34.75
54.5
80.78%
15.04
57.74
13.99
0.9855
11.90
40.60
54.5
99.89%
18.60
57.64
17.33
0.9854
14.80
50.50
58
58.87
0
0.03
58.27
0
0
1.7661
6.03
57.74
20.35%
3.61
58.13
3.50
0.9761
4.99
17.01
57.7
30.43%
5.37
58.07
5.24
0.9820
5.56
18.98
57.77
50.03%
8.79
57.97
8.63
0.9852
7.52
25.65
57.81
70.70%
12.40
57.81
12.23
0.9863
9.83
33.53
57.83
80.76%
14.16
57.73
13.99
0.9863
11.23
38.32
57.82
99.91%
17.50
57.65
17.33
0.9874
12.78
43.59