Vertiv
|
eSure™ Power Extend Converter Installation and User Manual (UM565050)
|
Rev. D
35
Table 8:
Front Panel Indicator Function and Alarm Contact State
Condition
LED
Color
Alarm Contact State
Power extend converter is
within correct input voltage
range and operating properly.
Green
Open Circuit
Low output voltage.
Red
Closed to Source Input
Bullet Terminal
Power Extend Converter fail.
Overcurrent Protection Mode.
Enable/Disable switch set to
off.
Output protected (HVSD).
Latched off due to
overcurrent.
No power to input.
Off
Closed to Source Input
Bullet Terminal
Blown fuse.