LD-16 Door Operator - Modernization
Install Electronic Edge
October 2021 - 88420 v.1.0
57
Install Electronic Edge
1. Install the electronic edge per the included instructions. See also:
Door Protection
Installation Manual
located on the Lobby.
2. Route cables—avoid tight bends and sharp edges—from the light curtain to the
ends of the door track, and secure with cable ties. See Figure 52 on page 58.
3. Use clips to secure the electronic edge cables to the doors.
4. Route the electronic edge cables up to the top of the door operator C-channel, and
secure with cable ties.
5. Route the electronic edge cables to the Door Operator Control Board located
behind the cover.
6. Plug in the cable from the receiver to X15 on the Door Operator Control Board.
7. Plug in the cable from the transmitter to X16 on the Door Operator Control Board.
See Electronic Edge Wiring.
Electronic Edge Wiring
The electronic edge is wired to the X15/X16 plugs on the door board (the quickest
response to edge activation).
DIP SW 2 controls how the door board responds when the edge activates.
•
When DIP SW 2 is ON and the edge activates: the door board will reopen the
doors, and the REOPEN relay output 3 at the X2 plug will also activate. The
REOPEN output can be wired to the controller’s electronic edge input to satisfy
that control need.
•
When DIP SW 2 is OFF and the edge activates: the door board will not reopen
the doors, but the REOPEN relay output 3 at the X2 plug will activate. The
REOPEN output contacts need to be wired to the controller’s electronic edge
input to achieve a door reopen.
If the electronic edge is wired directly to the controller—not to the X15/X16
plugs on the door board—the doors will only be allowed run at slow speed,
open and close. To achieve normal, full speed door cycles with an unused IPD
edge input, the door board must have a permanent jumper placed on the X15
plug, signal IPD to GND.