VC31LDVI/VC31CDVI Gas Fireplace Insert
12” (305 mm)
Maximum Depth
12”
(305 mm)
Side Wall
Combustible Mantel
Top Facing
Side Facing
3/4” (19 mm)
Maximum Depth
Combustible Facing
10” (254 mm)
Minimum
10” (254 mm)
Minimum
FP2964
insert clearances
9”
(228 mm)
CleARANCes
INseRt CleARANCes
No combustibles (ie: drapes, doors) may be within, or
swing within 36" of the front of the insert.
mANtel CleARANCes
NOte: the combustible area above the facing must
not protrude more than
3/4" (19 mm) from the facing.
If it does, it is considered a mantel and must meet the
mantel requirements listed in this manual.
FP2964
Figure 3 -
Mantel Clearances
NOte:
Side clearance
to combustibles is 10"
(254 mm) from opening
whether it is side wall or
mantel legs.
12"
(305 mm)
10"
(254 mm)
12" (305 mm)
4"
(101 mm)
3/4” (19 mm)
9"
(229 mm)
FP2965
mantel clearance
Finish Wall
FP2965
Figure 4 -
Mantel Clearances
Fireplace Insert
Opening
Noncombustible
Material Required
up to 9" Above
Fireplace Opening
heARth ReQuIRemeNts
The insert must be installed on a noncombustible hearth
extending a minimum of 10" (254 mm) from the fireplace
opening (local codes may require a larger hearth). The
hearth must also extend to both sides of the face.