VC31LDVI/VC31CDVI Gas Fireplace Insert

INstAllAtION 

INtAKe/exhAust  mANIFOlD  RemOVAl 

AND VeNt INstAllAtION

The intake/exhaust manifold is shipped attached to insert. 

It may be removed to allow tight installation. 
1.  Unfasten the two (2) machine screws on the face of the 

unit and release the plate assembly by sliding the plate 

back.

2.  Attach the exhaust and the intake flex pipes to the collar 

on the plates with a hose clamp (not provided) or other 

approved methods (check local codes). 

The  unit  is  shipped  from  the  factory  without  a  baffle 

installed. On the natural gas units, the baffle should be 

sufficient for venting up to 20 feet (6 m) off the top of the 

unit. An extra baffle plate is shipped with the unit for instal-

lations of 20 feet and above. 
Remove  four  (4)  screws  holding  baffle  plate. Add  extra 

baffle pate and reinstall screws. Align slots in baffle plates 

so the slots are closed. Retighten screws.

NOte:

 For propane (LP) units the baffle assembly is com-

pletely removed for venting under 20 ft. (6 m). For venting 

20 ft. and above, the baffle assembly is to be used with 

only one (1) baffle plate installed. 

Figure 17

FP1961
baffle adjustment
9/08

Loosen Four (4) Screws to Adjust

Bottom View

Closed position

Bottom View 

Open position

FP1961

Figure 17 - 

Baffle Assembly and Adjustment

3.  Slide  plate  assembly  back  in  place  under  locating 

tabs.

4.  While sliding unit in place, if necessary the glass latch/

shutoff tool can be used to help place the plate assem-

bly. Using the small end of the tool, insert it in the square 

notch in top front of firebox. Hook the plate assembly 

with tool and pull forward into place while sliding firebox 

to the rear. 

Figure 16

5.  Reinstall and tighten machine screws.

FP2977
latch tool plate assy

Plate 

Assembly

Latch Tool

FP2977

Figure 16

FP2979
intake exhaust

Figure 15

Machine 

Screws

Intake Collar

Exhaust/Intake 

Slide Plate 

Assembly

FP2979

Exhaust Collar

NO

te

Failure  to  install  the  baffle  assembly  on 

natural gas units may result in smaller than 

normal flame appearance.

Содержание VC31CDVINTSC

Страница 1: ...services or maintenance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier This applianc...

Страница 2: ...ff Tool 19 Electrical Installation 20 Electrical Wiring 20 Log Placement 21 Rock Wool Placement 21 Decorative Glass Glass Bead Installation 24 Operating Instructions 25 For Your Safety Read Before Lig...

Страница 3: ...installed by a qualified service person with glass door properly seated and sealed combustion leakage can occur CARBON MONOXIDE POISONING Early signs of carbon monoxide poisoning are similar to the fl...

Страница 4: ...from outside of the dwelling through the vent pipe These appliances have been tested by CSA and found to comply with the established standards for DIRECT VENT GAS FIREPLACE HEATERS in the USA and Cana...

Страница 5: ...certified without deration for elevations up to 4 500 feet 1 370 m above sea level For elevations above 4 500 feet 1 370 m in USA installation must be in accordance with the current ANSI Z223 1 NFPA 5...

Страница 6: ...ireplace Insert 2256QE 560 mm 115 6QE 303 mm 1056 257 mm 2 6QE 56 mm 55 6QE 144 mm 1656 410 mm 24 6QE 621 mm 2756 689 mm 256M 57 mm 2156QE 535 mm 4164 ICFDV insert dims insert dimensions Figure 2 VC31...

Страница 7: ...tion and clearances are subject to local building codes INSERT APPLICATIONS Before installing the gas fireplace insert consider the functioning needs of the fireplace Confirm the size of the fireplace...

Страница 8: ...g If it does it is considered a mantel and must meet the mantel requirements listed in this manual FP2964 Figure 3 Mantel Clearances NOTE Side clearance to combustibles is 10 254 mm from opening wheth...

Страница 9: ...BOX DIMS 22 6 568 mm 20 6M 527 mm 16 6M 426 mm 30 6M 781 mm 29N m 759 mm with control box and bracket removed REMOVE COMMAND CENTER BRACKET In order to fit insert into a smaller opening the command ce...

Страница 10: ...well ventilated OPEN ALL WINDOWS DURING INITIAL BURN OFF CURING PHASE Burn your insert for at least six 6 hours on HIGH the first time you use it Place the fan in the OFF position during this time Fp...

Страница 11: ...fore attempting installation Failure to do so could result in serious injury property damage or loss of life Operation of improperly installed and maintained venting system could result in serious inj...

Страница 12: ...d to resize orifice for use at high altitude contact your dealer High Temp Silicone FP2948 exhaust pipe 3 and 3 UL 1777 Gas Liner Apply high temperature silicone to lines on both ends and secure with...

Страница 13: ...let Recommended block off plate noncombustible metal Prevents odors from chimney entering room UL 127 Solid Fuel Z C Fire box Figure 11 Inlet and Exhaust Reline NOTE You may use a reline configuration...

Страница 14: ...els and retainers from packaging 2 Remove two 2 screws on each side of front edge of chamber 3 Install one 1 front brick retainer bracket on each side with the screws removed in Step 2 4 Carefully set...

Страница 15: ...celain Panel Kit Contemporary Porcelain Panel Kit Contemporary Support Bracket Supplied w Contem porary Kit Use Self tapping Screws Existing Support Figure 14 1 Remove porcelain panels and hardware fr...

Страница 16: ...e closed Retighten screws NOTE For propane LP units the baffle assembly is com pletely removed for venting under 20 ft 6 m For venting 20 ft and above the baffle assembly is to be used with only one 1...

Страница 17: ...ou must reduce incoming gas pressure to between 11 and 13 inches of water If you do not reduce incoming gas pressure burner system regula tor damage could occur Install external regulator with the ven...

Страница 18: ...contaminants This keeps them from going into the burner system gas con trols If sediment trap drip leg is not installed or is installed wrong burner system may not run properly NOTE The gas line conn...

Страница 19: ...ater and soap solution or a gas sniffer 4 To check gas pressures at valve turn captured screw counter clockwise 2 or 3 turns and then place tubing to pressure gauge over test point Turn unit to high F...

Страница 20: ...electrical supply Electricity is only needed to operate blower Verify proper operation after servicing Electrical connections should only be performed by a qualified licensed electrician Main power mu...

Страница 21: ...s will affect the flame and the flame appearance NOTE Embers may be added to entire burner area in front of grate to hide burner and log support brackets Ember Material Area LG1132 Figure 23 Ember Mat...

Страница 22: ...log on the right grate tine by placing the notch on the bottom of the log on the rear portion of the grate tine Figure 24 Log 3 LG1125 Figure 25 Log 4 LG1126 Figure 26 5 Install log 3 onto log 2 by pl...

Страница 23: ...notch on the bottom of the right side onto the middle or remaining rectangular protrusion on log 2 Figure 27 LG1128 CFDVI log 6 7 Log 6 LG1128 Figure 28 Log 7 8 Install log 6 by placing rectangular no...

Страница 24: ...is intended for future use 2 Mix the two 2 bags of decorative glass provided in the kit as desired Lay glass on top of burner and cover burner area with one 1 layer Glass may be used around the perim...

Страница 25: ...one Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will not fun...

Страница 26: ...s go to next step 4 Press the master switch to the ON position Within eight 8 seconds it will beep once This indicates the system is ready 5 Press ON button Sparker will spark and pilot flame will lig...

Страница 27: ...de and rear brick panels 2 Remove log support bracket by removing two 2 screws in rear and one 1 screw on each side wall FP1940 air shutter part open Air Shutter FP1940 Figure 30 Push Adjustment Lip U...

Страница 28: ...grate bar The slide adjustable air shutter has a range of 1 Figure 32 To increase air mixture open the slide adjustment by gently pulling on the lever When lever stops it has reached its maximum adju...

Страница 29: ...X Low battery Indication for Transmitter X Child Proof Lock out X LCD Backlight X Security Codes 16 X Countdown 6 hr Timer X Standard Thermostatic Control Mode X Smart Mode Thermostat Auto Flame Blowe...

Страница 30: ...n 3 seconds when the master switch Shutoff on the main burner is off RF Remote Receiver Push the RF receiver On Off button on the control board RF OFF On Off Beep once for ON and beep twice for OFF Le...

Страница 31: ...Learning GREEN Flashes every 1 sec for 10 sec AC Power On GREEN solid Pressure Switch Failed Power Vent only One RED every 2 sec until manual reset Self Diagnostics Chart The Command Center has a self...

Страница 32: ...arrows The blue LED backlight lights up for 8 seconds when any of the touch buttons is pressed The menus include TIMER THERMO LIGHT FAN and AUX Rear Burner Control The adjustment arrows include ON up...

Страница 33: ...e Command Cen ter will flash for 10 seconds 4 During the 10 sec onds press the OFF button on the transmitter to learn Another two beeps will be given to confirm a success ful learning Figure 38 TOUCH...

Страница 34: ...ireplace will be shut down completely when the timer counts down to zero 6 To exit Timer Mode a Push and hold the TIMER button for 3 seconds Or b Use the OFF down buttons to decrease the Set Time to z...

Страница 35: ...d OFF down button to increase de crease the blower speed 3 Press the fan button again to confirm the speed set ting If the fireplace is on the blower speed will take effect right away if the fireplace...

Страница 36: ...g is A touch any place in the touch area to bring up the icons then press TIMER but ton and THERMO button at the same time for 3 sec onds The backlight will flash once to indicate that the setting has...

Страница 37: ...play is blank 2 Check battery installation or replace batteries 3 LCD display shows funny display 3 Reset the transmitter see Resetting the Transmitter section 4 Appliance does not come on 2 The trans...

Страница 38: ...hey will damage the glass surface pilot and burner flames Visually check pilot and burner flames periodically Refer to Figure 48 for typical burner flame Refer to Figure 49 for typical pilot flame CLE...

Страница 39: ...Contact dealer where you bought heater 4 Remove rock wool Clean burner and burner ports Figure 51 5 Replace log set and ember according to instructions on Pages 21 23 Replace decorative glass accordi...

Страница 40: ...through Battery polarity wrong LED on the Command Center does not show solid green The 5 pin connector on the AC board broken or bent AC plug is plugged to AC mains Battery voltage low Using battery C...

Страница 41: ...0304166 VC31LDVI VC31CDVI Gas Fireplace Insert 41 REPLACEMENT PARTS 24 6 1 2 3 4 5 11 12 14 16 39 32 34 33 38 4166 VCFDVI31 parts 17 27 25 26 31 30 29 10 7 8 9 13 15 18 19 20 21 22 11 19 23 40 8 47 48...

Страница 42: ...0018 26 Command Center SCS 1 80D0005 80D0005 80D0005 27 AC Module SCS 1 80D0004 80D0004 80D0004 28 Remote Control 1 TSFRSC TSFRSC TSFSC 29 Wire Valve Control Board SCS 1 80D0010 80D0010 80D0010 30 Wir...

Страница 43: ...onversion Kits Natural Gas to LP VC31LDVINTSC Kit VCFILPK VC31CDVINTSC Kit ICF30LPK WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically ap...

Страница 44: ...TVI 5b Glass Frame Textured Mocha ICF30GTTM 6a Rectangular Double Door Satin Black ICF30R2DSB 6b Rectangular Double Door Vintage Iron ICF30R2DVI 6c Rectangular Double Door Textured Mocha ICF30R2DTM 7a...

Страница 45: ...20304166 VC31LDVI VC31CDVI Gas Fireplace Insert 45...

Страница 46: ...comply with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed Massachusetts Residents Only Plea...

Страница 47: ...ited 10 year warranty will be void if the appliance is not installed by a qualified installer in accor dance with the installation instructions The limited 10 year warranty will also be void if the ap...

Страница 48: ...rendement nerg tique de foyer au gaz nerguide Selon CSA P 4 1 09 Efficiency Ratings Model EnerGuide Ratings D O E Fireplace Efficiency AFUE VC31LDVINTSC 69 0 68 0 VC31LDVIPTSC 72 9 70 4 VC31CDVINTSC 6...

Отзывы: