background image

12

ODSR Series "A" Outdoor Woodburning Fireplace

20006811

FP270/271

CR Series

2/19/99   djt

Elbow Strap

Angled Strap

Fig. 18 

 Attach straps to a structural framing member.

FP270/271

Support Structure

Elbow Strap

(must be tight)

Ceiling Hole 

Framing

Angle Firestop

Chimney Support Strap

(must be tight)

Installing Outside Air Kit

An outside air kit is not installed in all ODSR Series "A" 

Fireplaces. If desired, or if local codes mandate the use 

of an air kit, then an AKU1 is required . If the outside air 

kit is to be used, the AKU1 

MUST

 be installed 

BEFORE

 

the fireplace is enclosed. Refer to the AKU1 instructions 

for field installation. 

NOTE:

 For Canada installations, model CCE-SK Chimney 

Collar Enclosure must be used on this fireplace with Model 

SK8 double wall chimney systems.

Installing the Chimney System

Start by attaching the first chimney section to the collar on 

top of the fireplace.

  

Install the pipe as pictured in Figure 17.  When  you get 

a good lock, you will hear the pipe clearly snap together. 

Once  sections  are  snap-locked  in  place,  it  is  extremely 

difficult to get them apart.  

Make sure the pipe is firmly 

snapped and locked together as each pipe section is 

mounted.

UP

FP558

BR

11/10/97

FP558

Fig. 17 

 Install pipe, listening for the snap-lock to fasten.

Pipe Section

Pipe 

Rim

Hem

Pipe 

Rim

Lance

Nail  the  firestop  spacer  (at  each  corner)  to  the  framing 

members of the ceiling hole. 

NOTE: 

 A firestop spacer is 

not required at the roof.
Hole sizes listed in Figure 13 for angled firestop spacers 

provide minimum required air space to chimney pipe for 

ceiling  thickness  up  to  8"  (203  mm).    When  combined 

thickness  of  ceiling  material,  ceiling  joists  and  flooring 

material exceeds 8" (203 mm), adjustments must be made 

in framing to assure that minimum air spaces to chimney 

are maintained.

Proper Firestop Spacer Installation

Figure 19 shows different installation procedures for  both 

an area that 

is

 an attic and  an area that 

is not

 an attic.

If the area above the ceiling

 is not 

an attic, position the 

firestop spacer with the flange on the ceiling side and the 

angled portion extending up into the hole.
If the area above the ceiling 

is

 an attic, position the firestop 

spacer with the flange on the top of the framed hole and 

the angled portion extending down into the hole.
Firestop spacers are not available for nor are they required 

on vertical walls.

DO NOT 

put any sealant around the area where the outer 

pipe slides through the firestop spacer.  If you seal this 

area,

 it may cause a fire hazard.

Canadian Requirements 

for Insulation Shield

In Canada, an attic insulation shield is required to prevent 

attic insulation from contacting the chimney section. Fram-

ing dimensions for the chimney hole should measure 14

¹⁄₂

x 14

¹⁄₂

" (368 x 368 mm). An attic shield MUST be installed 

on top of attic joists (above the floor level).  (Fig. 20) 

When  installing  elbows,  only  outer  pipe  will  snap-  lock.  

Middle pipes simply slide into position. Be sure to always 

attach straps on upper elbow to a structural framing mem-

ber. (Fig. 18)
Continue installing the pipe as required until pipe is installed 

up through the ceiling.  At this point, you must install a 

firestop spacer.

Installing the Firestop Spacer

 in the Ceiling hole

A firestop spacer is used to keep pipe spaced properly and 

required for safety.

Содержание ODSR36A

Страница 1: ...urning Fireplace For Models ODSR36A ODSR42A 948 SR cover 11 18 97 20006811 1 13 Rev 15 Homeowner s Installation and Operating Manual INSTALLER Leave this manual with the appliance CONSUMER Retain this manual for future refer ence ...

Страница 2: ...ing Safety Strips Securing the Fireplace 11 Installing Outside Air Kit 12 Installing the Chimney System 12 Finishing 14 Side Wall Protection 16 Hearth Installation 16 Installing Line for Gas Logs 18 Replacement Parts 19 Accessories 20 Chimney Components 21 Warranty 23 Table of Contents ODSR36A ODSR42A Listed UL 127 ULC S610 Standard for Factory Built Fireplaces Please read this manual before insta...

Страница 3: ...stible materials on any of the fireplace surround Burn only solid wood fuel or gas logs Do not install a solid fuel burning insert or other prod ucts not specified for use with this fireplace These fireplaces are not approved for installation in mobile homes This fireplace is not designed to be water tight There fore when installing this unit against an exterior wall the wall must be finished befo...

Страница 4: ...9 mm 2256O 572 mm 2656M 667 mm 43 6M 1111 mm 14 6 372 mm 11 279 mm 8 203 mm 756O 191 mm Outside Air Gas Line Access 8 Dia 203 mm 3 6 9 1 4 m m ODSR36A Series Woodburning Fireplace Fig 1 ODSR36A specifications and framing 36 914 mm 14 6 372 mm 11 279 mm 40 1016 mm 39 6 1006 mm 5 8 16 mm 5 8 1 6 m m 4856O 1232 mm 4856O 1232 mm 1 2 13 mm 1 2 6 8 5 6 O 1 7 4 0 m m 856M 210 mm 22 559 mm 2256O 572 mm 22...

Страница 5: ... cold climate not a requirement for unit operation or exterior installation FP554 Fig 5 Fireplace and chase parts identification Termination Cap Storm Collar Pan Flashing Batt Insulation cut out around firestop Firestop Ceiling Level Draftstop Ledge Bracket Surround Damper Control Gas Line Knockout both sides Screen Grate Firebox Metal Safety Strips 1 2 or 3 Outside Air Cover Plate Gas Line Access...

Страница 6: ... 9m Min NOTE If the fireplace is a freestanding unit it must be located a minimum of 10 3 m from the opening of the firebox to a combustible structure A minimum height of 6 4 1 9 m measured from the base of the firebox to the bottom of the termination cap is permitted FP1001 Fig 6 Freestanding installation ...

Страница 7: ...DSR42A Maximum 90 0 90 0 Minimum Without Elbows 12 6 12 6 With 2 Elbows 14 6 14 6 With 4 Elbows 21 0 21 0 B Do not use more than 4 elbows per chimney Attach the straps of the return top elbow to a structural framing member The offset first elbow of any pair does not have straps IWF269 C The chimney cannot be more than 30 45 in Canada from the vertical plane in any installation D The maximum length...

Страница 8: ...1 Planning the Chimney Run Determine how the chimney will be run length of run and chimney components required to complete the job Fig 8 Never install a chimney below minimum heights In planning a chimney system it is important to know 1 The height of a chimney is measured from the hearth to the exit point on the termination 2 Achimney cannot be offset more than 30 from a vertical plane 3 A chimne...

Страница 9: ...our Vermont Castings Group dealer for assistance FP284 Fig 10 Chimney support installation FP284 MBUF 5 25 96 Chimney Support Strap SKCS8 Insulating Fireplace Enclosure for Cold Climates If you live in a cold climate it is not required but highly recommended that you insulate fireplace enclosure to eliminate cold air penetration as much as possible Insulate base of fireplace with a noncombustible ...

Страница 10: ... Using a plumb bob positioned directly over center point of fireplace flue collar mark the ceiling to establish the chimney center point Fig 12 Offset Installation In order to clear an obstruction it may be necessary to offset chimney from vertical This is accomplished by us ing Vermont Castings Group elbows Use the 30 Offset Elbow table on Page 5 to determine proper offset and parts required Each...

Страница 11: ...s Securing the Fireplace Slide fireplace into position Lift the fireplace front slightly and slide the metal safety strips under front bottom edge about 1 38 mm allowing the remainder to extend in front of firebox Overlap strips at least 1 2 13 mm to provide a positive joint Flat safety strips are packed with fireplace Fig 15 FP557 BR 11 10 97 1 FP557 Fig 15 Safety strip installation 1 2 Min Overl...

Страница 12: ... chimney pipe for ceiling thickness up to 8 203 mm When combined thickness of ceiling material ceiling joists and flooring material exceeds 8 203 mm adjustments must be made in framing to assure that minimum air spaces to chimney are maintained Proper Firestop Spacer Installation Figure 19 shows different installation procedures for both an area that is an attic and an area that is not an attic If...

Страница 13: ...f Use same procedure detailed in locating centerpoint of the flue system Drive a nail up through roof at the center point This will determine center point on outside of the roof Cut and Frame Roof Hole Size of roof hole varies with the type of chimney termina tion installed Refer to installation instructions provided with Vermont Castings Group chimney termination to find correct size of roof hole...

Страница 14: ...p sides must be sealed with non combustible material to prevent cold air leakage into the room Only noncombustible material may be applied to the facing of the fireplace surround Black painted area Fig 21 Finish Wall Finish the wall with material of your choice Do not install a combustible mantel shelf less than 12 305 mm from the top of the fireplace opening Do not install a mantel face plate les...

Страница 15: ...surround to bottom of screen rail Finished Wall Header Standoff Noncombustible Material Radiant Surround Face Noncombustible Facing Material Radiant Surround Face 2 x 4 Stud Finished Wall Must be sealed with Noncombustible Material FP531a Fig 22 Mantel clearances MA81 Fig 23 Combustible mantel clearances MA81 156O Ref Combustible materials are permitted within a shaded area shown in Figure 24 titl...

Страница 16: ... mm Side Wall Protection Adjacent combustible side walls that are within the mini mum dimensions shown in Figure 24 of fireplace opening must be protected with Vermont Castings Group Wall Shield Model SP40 or a specifically built wall shield described below The special wall shield design described in Figure 20 is an alternate method of adding protection to side walls and can be used in place of th...

Страница 17: ...rmine the thickness required for any new mate rial NEW K of new material per inch Thickness required X of listed thickness K of listed material per inch material Example for Common Brick T new 5 0 0 458 x 0 50 in 5 46 in new required thickness COMMON MATERIALS AND FACTORS MATERIAL K R MINIMUM THICKNESS EH2416 Common Brick 0 458 5 0 1 09 0 50 in 0 10 5 46 in MHSC R Value is for 1 2 inch Units of K ...

Страница 18: ...ace Locate appropriate gas line in the outer casing of fireplace and remove insulation from gas line tube Fig 27 From inside the fireplace locate the knockout on the fire brick be sure you are on the appropriate or gas line side of the fireplace Using a flat bladed screwdriver or small chisel and hammer carefully tap around the knockout until it loosens and falls out Install 1 2 13 mm certified ga...

Страница 19: ...225 6a Firebrick Hearth 20005621 20005421 6b Firebrick Rear 20005627 20005462 6c Firebrick Right Side 20005626 20005461 6d Firebrick Left Side 20005625 20005460 6e Firebrick Ashlip 20005619 20005418 7 Top Brick Retainers three per fireplace 3030172 3030172 8 Cable Clips four per fireplace 20006869 20006869 9 Outer Collar Assembly SK8 Chimney 3030143 3030143 10 Basket Grate 20006701 20002230 11 O S...

Страница 20: ...tributor or dealer for fin ishing Marble and Mantels available in a wide selection of styles Accessory Descritpion Model Number Glass Door Standard Bi Fold set Brushed Brass finish 36GDKBBSR ODSR36A recommended for indoor use 42GDKBBSR ODSR42A Black finish 36GDKBKSR ODSR36A recommended for indoor use 42GDKBKSR ODSR42A Polished Brass finish 36GDKDBSR ODSR36A recommended for indoor use 36GDKDBSR ODS...

Страница 21: ...op Appropriate adapter required Flashing not included Adapter Kit Unites Square Chase Termination with chimney CTSK pipe required for CT100 cap Chase Top Housing Low profile pyramid style chimney cap used to PLTSK8 terminate chimney through a chase Includes adapter Flashing not included Chase Top Housing Square chimney cap used to terminate chimney SLTSK8 through a chase Terra Cotta Masonry Includ...

Страница 22: ...e air to assist in cooling the chimney system Attic Insulation Shield Used to prevent insulation from coming in AIS SK contact with the chimney system 45 Chimney Elbows Provides 45 offset and return For Canadian SK845 2 installations only For use with SK8 chimney only Maximum use of 2 or 1 pair Canada Model Number Description Component Chimney Components con t ...

Страница 23: ...ponents Cracks in ceramic and castable parts that do not affect safe operation We do not warrant this fireplace to be in compliance with your local building code Building codes vary greatly throughout the country and you should determine whether your local building code contains restrictions on the use of this fireplace before you purchase it Blowers or fans which are warranted separately Heat los...

Страница 24: ...Vermont Castings Group 149 Cleveland Drive Paris Kentucky 40361 www vermontcastingsgroup com ...

Отзывы: